b5-67: PID Diff Fdbk Monitor Lvl
No.
Name
(Hex.)
b5-67
PID Diff Fdbk
monitor Lvl
(11DF)
0 : Absolute
1 : +-
b5-89: Sleep Method Selection
No.
Name
(Hex.)
b5-89
Sleep Method
Selection
(0B89)
RUN
0 : Standard
1 : EZ Sleep/Wake-up
b5-90: EZ Sleep Unit
No.
Name
(Hex.)
b5-90
EZ Sleep Unit
(0B90)
0 : 0.1Hz units
1 : rev/min
b5-91: EZ Minimum Speed
No.
Name
(Hex.)
b5-91
EZ Minimum Speed
(0B91)
RUN
Note:
The unit of measure is determined by the setting value of b5-90 [EZ Sleep Unit]. This parameter is not automatically updated when b5-
90 is changed. Make sure to reconfigure this parameter if the setting value of b5-90 is changed.
b5-92: EZ Sleep Level
No.
Name
(Hex.)
b5-92
EZ Sleep Level
(0B92)
RUN
Note:
The unit of measure is determined by the setting value of b5-90 [EZ Sleep Unit]. This parameter is not automatically updated when b5-
90 is changed. Make sure to reconfigure this parameter if the setting value of b5-90 is changed.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Configures the signal level for the monitor selected with b5-63 [Differential
PID Feedback Select].
V/f
CL-V/f
OLV
CLV
AOLV
Configures the sleep and start operations modes when using the PID
function.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the unit of measure for b5-91 [EZ Minimum Speed] and b5-92
[EZ Sleep Level].
V/f
CL-V/f
OLV
CLV
AOLV
Configures the minimum speed for the EZ Sleep/Wake-up function. The
larger value between b5-91, b5-34 [PID Output Lower Limit], and d2-02
[Frequency Reference Lower Limit] is used internally to configure this
parameter.
V/f
CL-V/f
OLV
CLV
AOLV
The drive enters the sleep state when the output frequency or motor speed
drops below the value of b5-92 for a time longer than the setting value of
b5-93 [EZ Sleep Time].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.3 b: Application
Default Setting
(Range)
0
(0, 1)
Default Setting
(Range)
0
(0, 1)
Default Setting
(Range)
0
(0, 1)
Default Setting
(Range)
0.0 Hz or 0 min
-1
(r/
min)
(0.0 to 590.0 Hz or 0
to 35400 min
-1
(r/
min))
Default Setting
(Range)
-1
0.0 Hz or 0 min
(r/
min)
(0.0 to 590.0 Hz or 0
-1
to 35400 min
(r/
min))
11
633