YASKAWA GA700 Technical Manual page 797

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

The Run command source or frequency reference source is an external source selected with b1-01 [Frequency
Reference Selection 1], b1-02 [Run Command Selection 1], b1-15 [Frequency Reference Selection 2], or b1-16
[Run Command Selection 2].
3D: During Speed Search
Setting
Function
3D
During Speed Search
Note:
Refer to "b3: Speed Search" for more information.
3E: PID Feedback Low
Setting
Function
3E
PID Feedback Low
FbL [PID Feedback Loss] is detected when the PID feedback value falls below the setting value of b5-13 [PID
Feedback Loss Detection Lvl] for a time exceeding the setting value of b5-14 [PID Feedback Loss Detection
Time].
Note:
Refer to "PID Feedback Loss Detection" for more information.
3F: PID Feedback High
Setting
Function
3F
PID Feedback High
FbH [Excessive PID Feedback] is detected when the PID feedback value exceeds the setting value of b5-36 [PID
Feedback High Detection Lvl] for a time exceeding the setting value of b5-37 [PID Feedback High Detection
Time].
Note:
Refer to "PID Feedback Loss Detection" for more information.
4A: During KEB Ride-Thru
Setting
Function
4A
During KEB Ride-
Thru
Note:
Refer to "KEB Ride-Thru function" for more information.
4B: During Short Circuit Braking
Setting
Function
4B
During Short Circuit
Braking
Note:
• This function is enabled only when using PM motors while A1-02 = 8 [Control Method Selection = EZ Open Loop Vector Control].
• Refer to "b2: DC Circuit Braking" for more information.
4C: During Fast Stop
Setting
Function
4C
During Fast Stop
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when speed search is executing.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when FbL [PID Feedback Loss] is detected.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when FbH [Excessive PID Feedback] is detected.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on while the KEB Ride-Thru function is being executed.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on during Short Circuit Braking.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the fast stop is active.
11.8 H: Terminal Functions
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11
797

Advertisement