YASKAWA GA700 Technical Manual page 255

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

Register No.
(Hex.)
oFA1x Description (CN5-A)
bit 0
bit 1
bit 2
bit 3
00D9
bit 4
bit 5
bit 6
bit 7
bit 8 - F
00DA
Reserved
oFA3x Description (CN5-A)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
00DB
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E - F
oFb0x Description (CN5-B)
bit 0
bit 1
bit 2
00DC
bit 3 - 4
bit 5
bit 6
bit 7 - F
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
oFA10 [RAM Fault]
oFA11 [Option Operation Mode Fault (SLMOD)]
oFA12 [CRC Error (Drive receive)]
oFA13 [Frame Error (Drive receive)]
oFA14 [Abort Error (Drive receive)]
oFA15 [CRC Error (Option card receive)]
oFA16 [Frame Error (option card receive)]
oFA17 [Abort Error (option card receive)]
Reserved
oFA30 [Comm. ID Error]
oFA31 [Model Code Error]
oFA32 [Checksum Error]
oFA33 [Comm. option timeout waiting for response]
oFA34 [MEMOBUS/Modbus communications timeout]
oFA35 [Drive timeout waiting for response]
oFA36 [CI Check Error]
oFA37 [Drive timeout waiting for response]
oFA38 [Control Command Selection Error]
oFA39 [Drive timeout waiting for response]
oFA40 [Control Response Selection 1 Error]
oFA41 [Drive timeout waiting for response]
oFA42 [Control Response Selection 2 Error]
oFA43 [Drive timeout waiting for response]
Reserved
oFb00 [Not supported]
oFb01 [Option Connection Error]
oFb02 [DuplicateOptions]
Reserved
oFb05 [A/D Conversion Error]
oFb06 [Option Response Error]
Reserved
5.3 MEMOBUS/Modbus Communications
5
255

Advertisement

Table of Contents
loading

Table of Contents