YASKAWA GA700 Technical Manual page 786

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
0: During Run
Setting
Function
0
During Run
ON : Drive is running
The Run command is input, the drive is decelerating, or the DC injection braking is operating.
OFF : Drive is stopping
1: Zero Speed
Setting
Function
1
Zero Speed
Note:
The parameter used as the reference is determined by the setting of A1-02 [Control Method Selection].
A1-02 Settings
0
1
2
3
4
5
6
7
8
ON : The output frequency is less than the value of E1-09 or b2-01.
OFF : The output frequency is the value of E1-09 or more, or b2-01 or more.
786
V/f
CL-V/f
OLV
The terminal turns on when the Run command is input or the drive is outputting voltage.
Figure 11.85 Drive Running Time Chart
V/f
CL-V/f
OLV
The terminal turns on when the output frequency drops below the value of E1-09 [Minimum Output
Frequency] or b2-01 [DC Injection/Zero SpeedThreshold].
Description
V/f Control
Closed Loop V/f Control
Open Loop Vector Control
Closed Loop Vector Control
Advanced OpenLoop Vector Control
PM Open Loop Vector Control
PM Advanced Open Loop Vector
PM Closed Loop Vector Control
EZ Open Loop Vector Control
Figure 11.86 Zero Speed Time Chart
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
E1-09
E1-09
b2-01
E1-09
E1-09
E1-09
E1-09
b2-01
E1-09
Parameter used as the reference