YASKAWA GA700 Technical Manual page 732

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.7 F: Options
F6-01: Communication Error Selection
No.
Name
(Hex.)
F6-01
Communication Error
Selection
(03A2)
0 : Ramp to stop
The drive ramps the motor to stop according to the deceleration time. The terminal turns on when H2-xx = E
[MFDO Function Select = Fault] is set.
1 : Coast to stop
The drive shuts off output and the motor coasts to stop. The terminal turns on when H2-xx = E.
2 : Fast Stop (use C1-09)
The drive stops the motor using the deceleration time set in C1-09 [Fast Stop Time]. The terminal turns on when
H2-xx = E.
3 : Alarm only
bUS appears on the keypad, and operation continues in accordance with the current frequency reference.
Note:
Prepare safety protection equipment and systems such as fast stop switches separately.
4 : Alarm - run at d1-04
bUS appears on the keypad, and operation continues at the speed set in d1-04 [Reference 4].
Note:
Prepare safety protection equipment and systems such as fast stop switches separately.
5 : Alarm - Ramp Stop
The motor is stopped during the deceleration time set in C1-02 [Deceleration Time 1] when bUS issues are
detected.
When the bUS state clears, acceleration starts to return to the previous frequency reference.
F6-02: Comm External Fault (EF0) Detect
No.
Name
(Hex.)
F6-02
Comm External Fault
(EF0) Detect
(03A3)
0 : Always detected
1 : Detection during run only
F6-03: Comm External Fault (EF0) Select
No.
Name
(Hex.)
F6-03
Comm External Fault
(EF0) Select
(03A4)
0 : Ramp to stop
The drive ramps the motor to stop according to the deceleration time. The terminal turns on when H2-xx = E
[MFDO Function Select = Fault] is set.
1 : Coast to stop
The output shuts off and the motor coasts to stop. The terminal turns on when H2-xx = E.
2 : Fast Stop (use C1-09)
The drive stops the motor using the deceleration time set in C1-09 [Fast Stop Time]. The terminal turns on when
H2-xx = E.
3 : Alarm only
732
V/f
CL-V/f
OLV
CLV
AOLV
Selects the operation of the drive when bUS [Option Communication Error]
is detected.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the conditions at which EF0 [Option Card External Fault] is
detected.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the operation of the drive when EF0 [Option Card External Fault]
is detected.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
1
(0 - 5)
Default Setting
(Range)
0
(0, 1)
Default Setting
(Range)
1
(0 - 3)