YASKAWA GA700 Technical Manual page 693

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

HD: 2004 - 2021, 4002 - 4012
ND: 2004 - 2018, 4002 - 4009
7 : Variable Trq_60Hz base_50% mid V
This derated torque characteristics pattern is used for torque loads proportional to two times the rotation speed,
such as is the case with fans and pumps.
Note:
The voltage values in the figure represent those when using 200 V class drives. Double the values for 400 V class drives.
HD: 2004 - 2021, 4002 - 4012
ND: 2004 - 2018, 4002 - 4009
8 : High Start Trq_50Hz base_125% V
This pattern is used when moderate torque is required during startup.
Select this pattern only in the following circumstances.
• Wiring distance between the drive and motor is at least 150 m.
• An AC reactor is connected to the drive output.
Note:
The voltage values in the figure represent those when using 200 V class drives. Double the values for 400 V class drives.
HD: 2004 - 2021, 4002 - 4012
ND: 2004 - 2018, 4002 - 4009
9 : High Start Trq_50Hz base_165% V
This pattern is used when strong torque is required during startup.
Select this pattern only in the following circumstances.
• Wiring distance between the drive and motor is at least 150 m.
• An AC reactor is connected to the drive output.
Note:
The voltage values in the figure represent those when using 200 V class drives. Double the values for 400 V class drives.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
HD: 2030 - 2211, 4018 - 4103
ND: 2021 - 2169, 4012 - 4089
HD: 2030 - 2211, 4018 - 4103
ND: 2021 - 2169, 4012 - 4089
HD: 2030 - 2211, 4018 - 4103
ND: 2021 - 2169, 4012 - 4089
11.6 E: Motor Parameters
HD: 2257 - 2415, 4140 - 4675
ND: 2211 - 2415, 4103 - 4675
HD: 2257 - 2415, 4140 - 4675
ND: 2211 - 2415, 4103 - 4675
HD: 2257 - 2415, 4140 - 4675
ND: 2211 - 2415, 4103 - 4675
11
693