YASKAWA GA700 Technical Manual page 448

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.10 H: Terminal Functions
Setting
Function
42
Run Command (2-
Wire Sequence 2)
43
FWD/REV
Command (2-Wire
Seq 2)
44
Offset frequency 1
45
Offset frequency 2
46
Offset frequency 3
47
Node Setup
60
DC Injection
Braking command If the DC Injection Braking command is input when the drive is performing stopping
61
External Speed
Search command 1 Executes speed search using an external reference even when b3-01 = 0 [Speed Search
62
External Speed
Search command 2 Executes speed search using an external reference even when b3-01 = 0 [Speed Search
63
Field weakening
65
KEB Ride-Thru 1
(N.C.)
66
KEB Ride-Thru 1
(N.O.)
67
Communications
test mode
448
V/f
CL-V/f
OLV
CLV
AOLV
Inputs the Run command for 2-wire sequence 2. Use it paired with the FWD/REV
Command (2-Wire Seq 2) [H1-xx = 43].
ON : Run
OFF : Stop
Note:
Run Command (2-Wire Sequence 2) cannot be used at the same time as Forward/
Reverse Run Command (2-Wire Seq) [H1-xx = 40, 41].
V/f
CL-V/f
OLV
CLV
AOLV
Selects the direction of motor rotation for 2-wire sequence 2. Use it paired with the Run
Command (2-Wire Sequence 2) [H1-xx = 42].
ON : Reverse
OFF : Forward
Note:
FWD/REV Command (2-Wire Seq 2) cannot be used at the same time as Forward/
Reverse Run Command (2-Wire Seq) [H1-xx = 40, 41].
V/f
CL-V/f
OLV
CLV
AOLV
Adds the offset frequency set in d7-01 to the frequency reference. when the terminal is
turned ON.
V/f
CL-V/f
OLV
CLV
AOLV
Adds the offset frequency set in d7-02 to the frequency reference. when the terminal is
turned ON.
V/f
CL-V/f
OLV
CLV
AOLV
Adds the offset frequency set in d7-03 to the frequency reference. when the terminal is
turned ON.
V/f
CL-V/f
OLV
CLV
AOLV
When the CANopen communication option is utilized, the Node Setup function (a
function for setting the drive node address from the host controller) is enabled.
V/f
CL-V/f
OLV
CLV
AOLV
operation, DC Injection Braking is applied to stop the motor.
Note:
This function enables only when the induction motor is used for A1-02 = 8 [Control
Method Selection = EZ Open Loop Vector Control].
V/f
CL-V/f
OLV
CLV
AOLV
Selection at Start = Disabled].
Note:
If both H1-xx = 61 and 62 are set simultaneously, oPE03 [Multi-Function Input
Setting Err] is detected. Set the external speed search command for only 1 or 2.
V/f
CL-V/f
OLV
CLV
AOLV
Selection at Start = Disabled].
Note:
If both H1-xx = 61 and 62 are set simultaneously, oPE03 [Multi-Function Input
Setting Err] is detected. Set the external speed search command for only 1 or 2.
V/f
CL-V/f
OLV
CLV
AOLV
This function issues the commands of Field Weakening Level and Field Weakening
Frequency Limit set in d6-01 and d6-02 when the input terminal is turned ON
V/f
CL-V/f
OLV
CLV
AOLV
Switches the KEB1 function between enable and disable via the KEB Ride-Thru 1 (N.
C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
V/f
CL-V/f
OLV
CLV
AOLV
Switches the KEB1 function between enable and disable via the KEB Ride-Thru 1 (N.
O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
V/f
CL-V/f
OLV
CLV
AOLV
Performs self-diagnosis on the RS-485 serial communications operation.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Ref.
768
768
769
769
769
769
769
770
770
770
770
770
771