11.10 n: Special Adjustment
n8-62: Output Voltage Limit (for PM)
No.
Name
(Hex.)
n8-62
Output Voltage Limit
(for PM)
(057D)
Set so it is lower than the actual input power supply voltage.
n8-65: SpdFdbkDetectCtrlGainduringOVSup
No.
Name
(Hex.)
n8-65
SpdFdbkDetectCtrl
GainduringOVSup
(065C)
Adjust this parameter in the following circumstances.
• Increase the setting value if resonance or hunting occurs during use of the overvoltage suppression function.
• Reduce the setting value in increments of 0.05 if motor responsiveness is low during use of the overvoltage
suppression function.
n8-69: Speed Calculation Gain
No.
Name
(Hex.)
n8-69
Speed Calculation
Gain
(065D)
n8-72: Speed Estimation Method Select
No.
Name
(Hex.)
n8-72
Speed Estimation
Method Select
(0655)
0 : Conventional method
1 : A1000 method
n8-74: LghtLoadCurLvl 1
No.
Name
(Hex.)
n8-74
LghtLoadCurLvl 1
(05C3)
Note:
• If the condition n8-74 ≤ n8-75 [LghtLoadCurLvl 2] is not met, oPE08 [Parameter Selection Error] is displayed.
• Between n8-74 and n8-75 and the level of the pull-in current from n8-48 to n8-78 [MedLoad Id Level], the change is linear.
n8-75: LghtLoadCurLvl 2
No.
Name
(Hex.)
n8-75
LghtLoadCurLvl 2
(05C4)
894
V/f
CL-V/f
OLV
CLV
AOLV
To prevent saturation of the output voltage, set the output voltage limit.
Normally there is no need to configure this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of internal speed feedback detection suppression while the
overvoltage suppression function is working, as a magnification value.
Normally there is no need to configure this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain used for speed estimation. Normally there is no need to change
this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the speed estimation method. Normally there is no need to change
this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Set n8-48 [Pull-In Current (for PM Motors)] to the level of the load current
(q-axis current) to be applied.
V/f
CL-V/f
OLV
CLV
AOLV
Set n8-78 [MedLoad Id Level] to the level of the load current (q-axis
current) to be applied.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default Setting
(Range)
200 V Class: 200.0 V,
400 V Class: 400.0 V
(200 V Class: 0.0 -
230.0 V, 400 V Class:
0.0 - 460.0 V)
Default Setting
(Range)
1.50
(0.00 - 10.00)
Default Setting
(Range)
1.00
(0.00 - 20.00)
Default Setting
(Range)
1
(0, 1)
Default Setting
(Range)
30%
(0 - 255%)
Default Setting
(Range)
50%
(0 - 255%)