YASKAWA GA700 Technical Manual page 695

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

HD: 2004 - 2021, 4002 - 4012
ND: 2004 - 2018, 4002 - 4009
D : High Freq_60Hz base_120Hz max
This pattern is used to rotate motors at greater than 60 Hz. Output voltage is constant when operating at greater
than 60 Hz.
Note:
The voltage values in the figure represent those when using 200 V class drives. Double the values for 400 V class drives.
HD: 2004 - 2021, 4002 - 4012
ND: 2004 - 2018, 4002 - 4009
E : High Freq_60Hz base_180Hz max
This pattern is used to rotate motors at greater than 60 Hz. Output voltage is constant when operating at greater
than 60 Hz.
Note:
The voltage values in the figure represent those when using 200 V class drives. Double the values for 400 V class drives.
HD: 2004 - 2021, 4002 - 4012
ND: 2004 - 2018, 4002 - 4009
F : Custom
Enables a custom V/f pattern by changing E1-04 through E1-13 [V/f Pattern for Motor 1].
The default settings are equivalent to setting value 1 [Constant Trq_60Hz base_60Hz max].
E1-04: Maximum Output Frequency
No.
Name
(Hex.)
E1-04
Maximum Output
Frequency
(0303)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
HD: 2030 - 2211, 4018 - 4103
ND: 2021 - 2169, 4012 - 4089
HD: 2030 - 2211, 4018 - 4103
ND: 2021 - 2169, 4012 - 4089
HD: 2030 - 2211, 4018 - 4103
ND: 2021 - 2169, 4012 - 4089
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum output frequency for the V/f pattern.
HD: 2257 - 2415, 4140 - 4675
ND: 2211 - 2415, 4103 - 4675
HD: 2257 - 2415, 4140 - 4675
ND: 2211 - 2415, 4103 - 4675
HD: 2257 - 2415, 4140 - 4675
ND: 2211 - 2415, 4103 - 4675
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.6 E: Motor Parameters
Default Setting
(Range)
Determined by A1-02
and E5-01
(Determined by A1-
02 and E5-01)
695