YASKAWA GA700 Technical Manual page 793

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

18: Torque Detection 2 (N.O.)
Setting
Function
18
Torque Detection 2
(N.O.)
Configure the torque detection with parameter L6 [Torque Detection].
ON : The output current/torque exceeds the torque value set with L6-05 [Torque Detection Level
2], or the level has dropped and remained in this state longer than the time set with L6-06 [Torque
Detection Time 2].
Note:
• When configured such that L6-04 ≥ 5, the state in which the output current/torque is less that the detection level of L6-05 is detected
when the time set with L6-06 has elapsed.
• Refer to "L6: Torque Detection" for more information.
19: Torque Detection 2 (N.C.)
Setting
Function
19
Torque Detection 2
(N.C.)
Configure the torque detection with parameter L6 [Torque Detection].
OFF : The output current/torque exceeds the torque value set with L6-05 [Torque Detection Level
2], or the level has dropped and remained in this state longer than the time set with L6-06 [Torque
Detection Time 2].
Note:
• When configured such that L6-04 ≥ 5, the state in which the output current/torque is less that the detection level of L6-05 is detected
when the time set with L6-06 has elapsed.
• Refer to "L6: Torque Detection" for more information.
1A: During Reverse
Setting
Function
1A
During Reverse
ON : The motor is running in reverse.
OFF : The motor is running forward or is stopped.
1B: During Baseblock (N.C.)
Setting
Function
1B
During Baseblock (N.
C.)
ON : The drive is not in the baseblock state.
OFF : During baseblock
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when an overtorque/undertorque situation is detected.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns off when an overtorque/undertorque situation is detected.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the motor runs in reverse.
Figure 11.95 Reverse Operation Output Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns off during baseblock. When the drive is in the baseblock state, the drive output
transistor stops switching, and the DC bus voltage is not output.