F2: Analog Input Option - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.7 F: Options
0 : A pulse detection
1 : AB pulse detection
F1-50: Encoder Selection
No.
Name
(Hex.)
F1-50
Encoder Selection
(03D2)
0 : EnDat Sin/Cos
1 : EnDat SerialOnly
2 : Hiperface
F1-51: PGoH Detection Level
No.
Name
(Hex.)
F1-51
PGoH Detection
Level
(03D3)
PGoH is detected when the value of
For expression
represents the single-track (phase A) output from the encoder.
Note:
This function is enabled when F1-20 = 1 [PG Hardware Disconnection Detection Selection = Enabled].
F1-52: Serial Encoder Communication bps
No.
Name
(Hex.)
F1-52
Serial Encoder
Communication bps
(03D4)
Note:
This function is enabled when F1-50 = 1 or 2 [Encoder Selection = EnDat SerialOnly or Hiperface].
0 : 1M/9600bps
1 : 500k/19200bps
2 : 1M/38400bps

F2: Analog Input Option

F2 parameters are used to set the operation of the drive when using the analog input option card AI-A3. The AI-
A3 card has 3 input terminals that accept voltages of -10 V to +10 V (20 kΩ) or currents of 4 mA to 20 mA (250
Ω). Installing the AI-A3 card into the drive enables the settings of highly precise analog references with high
resolution.
Refer to the instruction manual packaged with the AI-A3 card for more information on installing, wiring, and
setting the AI-A3 card.
WARNING! Sudden Movement Hazard. Perform test runs and periodic inspections to ensure that command references are
configured appropriately. Incorrect configuration of the command reference can cause unintended motor rotation, which may
lead to equipment damage or injury.
F2-01: Analog Input Function Selection
No.
Name
(Hex.)
F2-01
Analog Input
Function Selection
(038F)
718
V/f
CL-V/f
OLV
CLV
AOLV
Selects the encoder connected to PG-F3.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for PGoH [PG Hardware Fault]
of PG-F3 as a percentage when XXX is 100%.
falls below the level set in F1-51.
, Sin θ represents the single-track (phase B) output from the encoder and Cos θ
V/f
CL-V/f
OLV
CLV
AOLV
Selects the speed of communication between the PG-F3 and serial encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the input method for the analog reference used with AI-A3.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default Setting
(Range)
0
(0 - 2)
Default Setting
(Range)
80%
(1 - 100%)
Default Setting
(Range)
0
(0 - 2)
Default
(Range)
0
(0, 1)