11.8 H: Terminal Functions
OFF : b1-01 = [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
3: Multi-Step Speed Reference 1
Setting
Function
3
Multi-Step Speed
Reference 1
Note:
Refer to the "Setting Procedures for Multi-step Speed Operation" of the d-parameter for details.
4: Multi-Step Speed Reference 2
Setting
Function
4
Multi-Step Speed
Reference 2
Note:
Refer to the "Setting Procedures for Multi-step Speed Operation" of the d-parameter for details.
5: Multi-Step Speed Reference 3
Setting
Function
5
Multi-Step Speed
Reference 3
Note:
Refer to the "Setting Procedures for Multi-step Speed Operation" of the d-parameter for details.
6: Jog Reference Selection
Setting
Function
6
Jog Reference
Selection
7: Accel/decel Time Selection 1
Setting
Function
7
Accel/decel Time
Selection 1
Note:
Refer to "C1: Accel & Decel Time" for details.
8: Baseblock Command (N.O.)
Setting
Function
8
Baseblock Command
(N.O.)
The keypad flashes bb [Baseblock]. If the baseblock command is canceled when the Run command is ON, the
drive restarts the motor utilizing the speed search function.
WARNING! Sudden Movement Hazard. If using the Baseblock command with hoist-type application, make sure the holding
brake is closed when the Baseblock command is input and the drive shuts off its output. Failure to do so may result in the motor
suddenly coasting when the Baseblock command is input, which may result in the load slipping or falling.
758
V/f
CL-V/f
OLV
CLV
AOLV
Switches d1-01 to d1-08 [Multi-Step Speed Reference] using a combination of multi-step speed
references 1, 2 and 3.
V/f
CL-V/f
OLV
CLV
AOLV
Switches d1-01 to d1-08 [Multi-Step Speed Reference] using a combination of multi-step speed
references 1, 2 and 3.
V/f
CL-V/f
OLV
CLV
AOLV
Switches d1-01 to d1-08 [Multi-Step Speed Reference] using a combination of multi-step speed
references 1, 2 and 3.
V/f
CL-V/f
OLV
CLV
AOLV
Enables the Jog Reference (JOG command) that was set ind1-17. The Jog Reference (JOG
command) overrides even References 1 to 16 (d1-01 to d1-16).
V/f
CL-V/f
OLV
CLV
AOLV
Switches between C1-01, C1-02 [Acceleration/Deceleration Time 1] and C1-03, C1-04
[Acceleration/Deceleration Time 2].
V/f
CL-V/f
OLV
CLV
AOLV
If a baseblock command (N.O.) is input, the drive output will stop and the motor will coast to stop.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV

Advertisement