YASKAWA GA700 Technical Manual page 726

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.7 F: Options
F4-03: Terminal V2 Monitor Selection
No.
Name
(Hex.)
F4-03
Terminal V2 Monitor
Selection
(0393)
Enter the final three digits of Ux-xx [Monitors] to determine which monitor data is output from the option card.
For example, to monitor U1-03 [Output Current], set a value of 103.
Note:
• Some monitors are only available in certain control methods.
• Set 000 or 031 when using the terminal in through mode. The terminal V2 output level can be set from the PLC via MEMOBUS/
Modbus or the communication option.
F4-04: Terminal V2 Monitor Gain
No.
Name
(Hex.)
F4-04
Terminal V2 Monitor
Gain
(0394)
RUN
The maximum output voltage output from terminal V2 is ±10 V. The signal level can be selected with F4-08
[Terminal V2 Signal Level].
Setting example:
When set as follows, and the monitored output voltage is at 100% (drive rated current), the output voltage of
terminal V2 is 5 V (50% of 10 V). Thus, the output current is 200% of the drive rated current when terminal V2
outputs a maximum voltage of 10 V.
• F4-03 [Terminal V2 Monitor Selection] = 103 (U1-03: Output Current)
• F4-04 = 50.0%
• F4-06 [Terminal V2 Monitor Bias] = 0.0%
• F4-08 = 0 (0 to 10 V)
F4-05: Terminal V1 Monitor Bias
No.
Name
(Hex.)
F4-05
Terminal V1 Monitor
Bias
(0395)
RUN
The maximum output voltage output from terminal V1 is ±10 V. The signal level can be selected with F4-07
[Terminal V1 Signal Level].
F4-06: Terminal V2 Monitor Bias
No.
Name
(Hex.)
F4-06
Terminal V2 Monitor
Bias
(0396)
RUN
The maximum output voltage output from terminal V2 is ±10 V. The signal level can be selected with F4-08
[Terminal V2 Signal Level].
726
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number for monitor item of output from terminal V2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of monitor signal output from terminal V2 as a percentage.
Sets the voltage level output from terminal V2 to a 100% value of 10 V
when a monitoring item is at 100% while an output of 0% for monitoring
items is 0 V.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of monitor signal output from terminal V1 as a percentage.
Sets the voltage level output from terminal V1 to a 100% value of 10 V
when the output for monitoring items is 0%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of monitor signal output from terminal V2 as a percentage.
Sets the voltage level output from terminal V2 to a 100% value of 10 V
when the output for monitoring items is 0%.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default Setting
(Range)
103
(000 - 999)
Default Setting
(Range)
50.0%
(-999.9 - +999.9%)
Default Setting
(Range)
0.0%
(-999.9 - +999.9%)
Default Setting
(Range)
0.0%
(-999.9 - +999.9%)