YASKAWA GA700 Technical Manual page 760

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
OFF : Terminal selected with H3-14 is disabled
D: PG Encoder Disable
Setting
Function
D
PG Encoder Disable
ON : Speed feedback control disable (V/f Control)
OFF : Speed feedback control enable (Closed Loop V/f Control)
E: ASR Integral Reset
Setting
Function
E
ASR Integral Reset
ON : P control
OFF : PI control
F: Through Mode
Setting
Function
F
Through Mode
The through mode is a function that uses the signal input to the terminal as a digital input for the upper sequence
via a communication option or MEMOBUS/Modbus communications. This input signal does not affect drive
operation.
10: Up Command
Setting
Function
10
Up Command
ON : Raises the frequency reference.
OFF : Holds the current frequency reference.
Note:
• If only one of either the Up command or Down command has been set, oPE03 [Multi-Function Input Setting Err] will be detected.
• If two or more of the following functions have been allocated at the same time, oPE03 occurs.
–Up/Down command
–Accel/Decel Ramp Hold
–Reference sample hold
–Offset Frequency 1, 2, 3 addition
–Up/Down 2 Command
• The Up/Down command can be used when the keypad is in REMOTE mode or b1-01 ≠ 0 [Frequency Reference Selection 1 ≠
Keypad].
• The Up/Down command does not function when switching to parameter b1-15 [Frequency Reference Selection 2] using External
Reference 1/2 Selection [H1-xx = 2].
If the Up command is input, the frequency reference increases, and if Down command is input, the frequency
reference decreases.
Up and Down command has priority over all other frequency references. When the Up/Down command is
enabled, the following frequency references will be disregarded.
• Frequency reference from Keypad [b1-01 = 0]
• Frequency reference from Analog Input [b1-01 = 1]
• Frequency reference from Pulse Train Input [b1-01 = 4]
The table below shows the Up and Down commands with their corresponding operation.
760
V/f
CL-V/f
OLV
CLV
AOLV
Disregards feedback control from the encoder and runs V/f Control run if the terminal is turned
ON. Controls the motor speed using feedback from the encoder if the terminal is turned OFF.
V/f
CL-V/f
OLV
CLV
AOLV
Resets the integral value and switches the speed control loop between PI control and P control.
V/f
CL-V/f
OLV
CLV
AOLV
Set when a terminal is not used or when using a terminal in through mode.
V/f
CL-V/f
OLV
CLV
AOLV
It is paired with setting value 11 (Down command). When using the Up command and Down
command, the user can raise and lower the frequency reference of the drive using two push buttons.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM