Advertisement

5.3 MEMOBUS/Modbus Communications
Make sure terminal SC and terminal SP are connected by a wire jumper.
Figure 5.7 Terminal Connection of the Communication Part when Performing Self-Diagnostics
5.
Energize the drive.
6.
When normal, PASS [MEMOBUS/Modbus Communications Test Mode Normal] is displayed on the
keypad.
When there is an error, CE [MEMOBUS/Modbus Communications Error] is displayed on the keypad.
7.
De-energize the drive.
8.
Disconnect the wire jumper from terminal S6-SN. Also, set terminal S6 to its original function.
9.
Self-Diagnostics is completed and returns to normal functionality.

Communications Data Table

The following table lists the communications data. The data types are command data, monitor data, and broadcast
message.
The communications registers for the parameter numbers are listed on the "Parameter List."
Command Data
The command data can be read and written.
Note:
Set the reserved bit to 0. Also, do not write the data in the reserved register and the monitor register.