YASKAWA GA700 Technical Manual page 247

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

Register No.
(Hex.)
0031
U1-07 [DC Bus Voltage] (Units: 1 V)
0032
U1-09 [Torque Reference] (Units: 1%)
0033
Reserved
0034
Product code 1 [ASCII], product type (GA700 =0A)
0035
Product code 2 [ASCII], region
0036 - 0037
Reserved
0038
PID Feedback: Unsigned, input is equivalent to 100%/maximum output frequency (Units:0.1%)
0039
PID Input: Unsigned, ±100%/±maximum output frequency (Units:0.1%)
003A
PID Output: Unsigned, ±100%/±maximum output frequency (Units:0.1%)
003B - 003C Reserved
Communications error description
Note:
The description of the communications error is saved until the fault is reset.
bit 0
bit 1
bit 2
003D
bit 3
bit 4
bit 5
bit 6
bit 7 - F
003E
Output frequency
003F
0040 - 004A Used with U1-xx [Operation Status Monitors. Refer to the U Monitor for details.
U1-12 [Drive Status]
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
004B
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit E
bit F
004C - 007E Use with U1-xx, U4-xx, U5-xx, U6-xx [Monitors]. Refer to "U2: Fault Trace" and "U3: Fault History" for details.
Minor fault code (Refer to "Minor fault description" for more information on the minor fault codes.)
007F
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
CRC Error
Data Length Error
Reserved
Parity Error
Overrun Error
Framing Error
Timeout
Reserved
Units: min
-1
or r/min
Note:
Set E2-04, E4-04, E5-04, E9-08 [Motor Pole Count].
0.01%
1: During run
1: During zero speed
1: During reverse
1: During reset signal input
1: During speed agreement
1: Drive operation ready
1: Minor Fault
1: Fault
1: oPExx [Operation Error] generation
1: Recovery from momentary power loss, 0: Power recovery
1: Motor 2 Selection
Reserved
ComRef status/ NetRef status
ComCtrl status/ NetCtrl status
5.3 MEMOBUS/Modbus Communications