H4: Analog Outputs - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

H4: Analog Outputs

No.
Name
(Hex.)
H4-01
Terminal FM
Analog Output
(041D)
Select
H4-02
Terminal FM
Analog Output
(041E)
Gain
RUN
H4-03
Terminal FM
Analog Output
(041F)
Bias
RUN
H4-04
Terminal AM
Analog Output
(0420)
Select
H4-05
Terminal AM
Analog Output
(0421)
Gain
RUN
H4-06
Terminal AM
Analog Output
(0422)
Bias
RUN
H4-07
Terminal FM
Signal Level Select Selects the output signal level from the MFAO terminal FM.
(0423)
H4-08
Terminal AM
Signal Level Select Selects the signal level output from the MFAO terminal AM.
(0424)
H4-20
Output power
monitor level
(0B53)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitoring number to be output from multi-function analog
output terminal FM.
Set the x-xx portion of the monitoring parameter Ux-xx. For
example, set x-xx to 102 to monitor U1-02 [Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the monitoring signal that is output from the MFAO
terminal FM as a percentage. Set the terminal FM output signal
level when an output of 0% for monitoring items is 0 V (or 4 mA)
and when an output for monitoring items is 100%, and sets 10 V (or
20 mA) as 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitoring signal that is output from the MFAO
terminal FM as a percentage. Set the level of the analog signal
output from the FM terminal at 10 V (or 20 mA) as 100% when an
output for monitoring items is 0%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitoring number to be output from the MFAO terminal
AM.
Set the x-xx portion of the monitoring parameter Ux-xx. For
example, set x-xx to 102 to monitor U1-02 [Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the monitor signal that is output from the MFAO
terminal AM as a percentage. Sets the level of the analog signal
output from the AM terminal when an output of 0% for monitoring
items is 0 V (or 4 mA) and when an output for monitoring items is
100%, and sets 10 V (or 20 mA) as 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitoring signal that is output from the MFAO
terminal AM as a percentage. Set the level of the analog signal
output from the AM terminal at 10 V (or 20 mA) as 100% when an
output for monitoring items is 0%
V/f
CL-V/f
OLV
CLV
AOLV
Note:
Set jumper S5 on the terminal board accordingly when changing
these parameters.
0 : 0 to 10 Vdc
1 : -10 to +10 Vdc
2 : 4 to 20 mA
V/f
CL-V/f
OLV
CLV
AOLV
Note:
Set jumper S5 on the terminal board accordingly when changing
these parameters.
0 : 0 to 10 Vdc
1 : -10 to +10 Vdc
2 : 4 to 20 mA
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level at 10 V when U1-08 [Output Power] executes analog
output.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
10.10 H: Terminal Functions
Default
Ref.
(Range)
102
814
(000 - 999)
100.0%
814
(-999.9 - 999.9%)
0.0%
815
(-999.9 - 999.9%)
103
815
(000 - 999)
50.0%
815
(-999.9 - 999.9%)
0.0%
815
(-999.9 - 999.9%)
0
816
(0 - 2)
0
816
(0 - 2)
0.00 kW
816
(0.00 - 650.00 kW)
10
461