YASKAWA GA700 Technical Manual page 908

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.11 o: Keypad-Related Settings
o4-01: Cumulative Operation TimeSetting
No.
Name
(Hex.)
o4-01
Cumulative
Operation
(050B)
TimeSetting
Selecting o4-01 on the keypad displays the current value of U4-01 in units of 10 hours (h). When the setting of
o4-01 is changed via the monitor, the recount of U4-01 starts in accordance with the setting of o4-01.
Note:
Parameter o4-01 is configured in units of 10 hours (h). When o4-01 = 30, U4-01 [Cumulative Ope Time] = 300 h appears.
o4-02: Cumulative Operation Time Select
No.
Name
(Hex.)
o4-02
Cumulative
Operation Time
(050C)
Select
0 : Logs power-on time
Counts the time when the drive is energized up to when it is de-energized.
1 : Running Time
Counts the time that the drive outputs voltage.
o4-03: CoolingFan OperationTime Setting
No.
Name
(Hex.)
o4-03
CoolingFan
OperationTime
(050E)
Setting
The cumulative cooling fan operation time can be monitored with U4-03 [Cooling Fan Ope Time]. If a cooling
fan is replaced, make sure to set o4-03 = 0 and reset the value of U4-03. Selecting o4-03 on the keypad displays
the current value of U4-03 in units of 10 hours (h). When the setting of o4-03 is changed via the monitor, the
recount of U4-03 starts in accordance with the setting of o4-03.
Note:
Parameter o4-03 is configured in units of 10 hours (h). When o4-03 = 30, U4-03 [Cooling Fan Ope Time] = 300 h appears.
o4-05: Capacitor Maintenance Setting
No.
Name
(Hex.)
o4-05
Capacitor
Maintenance Setting
(051D)
If a drive is replaced, make sure to set o4-05 = 0 and reset the value of U4-05. When the setting of o4-05 is
changed, the recount of U4-05 starts in accordance with the setting of o4-05. Once the configuration is complete,
the setting value of o4-05 automatically resets to 0.
Note:
The maintenance period differs depending on the environment in which the drive is used.
o4-07: DCBusPreChargeRelayMainteSetting
No.
Name
(Hex.)
o4-07
DCBusPreChargeRe
layMainteSetting
(0523)
908
V/f
CL-V/f
OLV
CLV
AOLV
Configures the initial value of the cumulative drive operation time in units
of 10 hours.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the condition used to count the cumulative operation time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value from which to start the cumulative drive cooling fan
operation time in 10-hour units.
V/f
CL-V/f
OLV
CLV
AOLV
U4-05 [CapacitorMaintenance] monitor values can be overwritten.
V/f
CL-V/f
OLV
CLV
AOLV
U4-06 [SChgBypassRelayMaint] monitor values can be overwritten.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0 h
(0 - 9999 h)
Default Setting
(Setting Range)
0
(0, 1)
Default Setting
(Setting Range)
0 h
(0 - 9999 h)
Default Setting
(Setting Range)
0%
(0 - 150%)
Default Setting
(Setting Range)
0%
(0 - 150%)