bUS appears on the keypad, and operation continues.
Note:
Prepare safety protection equipment and systems such as fast stop switches separately.
■
F6-04: bUS Error Detection Time
No.
Name
(Hex.)
F6-04
bUS Error Detection
Time
(03A5)
Note:
The setting value changes to 0.0 s when the option card is mounted in the drive.
■
F6-06: Torque Reference/Limit by Comm
No.
Name
(Hex.)
F6-06
Torque Reference/
Limit by Comm
(03A7)
0 : Disabled
1 : Enabled
■
F6-07: Multi-Step Ref @ NetRef/ComRef
No.
Name
(Hex.)
F6-07
MultiStep Ref
Priority Select
(03A8)
0 : MultiStep References Disabled
The multi-step speed reference (2-step speed to 16-step speed references) and the Jog Frequency Reference (JOG
command) are disabled when NetRef or ComRef is selected as the frequency reference source.
1 : MultiStep References Enabled
The multi-step speed reference (2-step speed through 16-step speed references) and the Jog Frequency Reference
(JOG command) are enabled, and the frequency reference can be changed when NetRef or ComRef is selected as
the frequency reference source.
■
F6-08: Comm Parameter Reset @Initialize
No.
Name
(Hex.)
F6-08
Comm Parameter
Reset @Initialize
(036A)
Note:
The setting value of F6-08 is not changed when the drive is initialized by A1-03 when F6-08 = 1.
0 : No Reset - parameters retained
1 : Reset - back to factory default
■
F6-10: CC-Link Node Address
No.
Name
(Hex.)
F6-10
CC-Link Node
Address
(03B6)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the delay time until bUS [Option Communication Error] issues are
detected.
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether to enable or disable the torque reference and torque limit
received from the communication option card.
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether to enable/disable the multi-step speed reference when
NetRef (communication option card) or ComRef (MEMOBUS/Modbus
communications) is selected as the frequency reference source.
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether or not to initialize communication parameters [F6-xx and
F7-xx] when the drive is initialized by A1-03 [Initialize Parameters].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node address for CC-Link communication. The drive must be
restarted when the setting is changed.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.7 F: Options
Default Setting
(Range)
2.0 s
(0.0 - 5.0 s)
Default Setting
(Range)
0
(0, 1)
Default Setting
(Range)
0
(0, 1)
Default Setting
(Range)
0
(0, 1)
Default Setting
(Range)
0
(0 - 64)
11
733