o3: Copy Function

No.
Name
(Hex.)
o3-01
Copy Function
Selection
(0515)
o3-02
Copy Allowed
Selection
(0516)
o3-04
Select Backup/
Restore Location
(0B3E)
o3-05
Select items to
Backup/Restore
(0BDA)
o3-06
Auto Parameter
Backup Selection
(0BDE)
o3-07
Period setting of
auto backup
(0BDF)

o4: Maintenance Mon Settings

No.
Name
(Hex.)
o4-01
Cumulative
Operation
(050B)
TimeSetting
o4-02
Cumulative
Operation Time
(050C)
Select
o4-03
CoolingFan
OperationTime
(050E)
Setting
o4-05
Capacitor
Maintenance
(051D)
Setting
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Drive parameters can be saved and copied to another drive using the
keypad.
0 : Copy select
1 : Drive → Keypad Backup
2 : Keypad → Drive Restore
3 : Keypad ←→ Drive (compare)
V/f
CL-V/f
OLV
CLV
AOLV
Selects the enabled/disabled status of backup when o3-01 = 1 [Copy
Function Selection = Drive → Keypad Backup].
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Selects the storage region for drive parameters when backing up and
restoring parameters. This parameter is only enabled for LED
keypads.
0 : Memory Location 0
1 : Memory Location 1
2 : Memory Location 2
3 : Memory Location 3
V/f
CL-V/f
OLV
CLV
AOLV
Selects the parameters that are backed up, restored, and referenced.
This parameter is only enabled for LED keypads.
0 : Standard Parameters
1 : Standard + DWEZ Parameters
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether to enable or disable the automatic parameter backup
function. This parameter is only enabled for LED keypads.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Configures the interval at which the automatic parameter backup
function saves parameters from the drive to the keypad.
Note:
This parameter is only enabled for LED keypads.
0 : every 10 minutes
1 : every 30 minutes
2 : every 60 minutes
3 : every 12 hours
Description
V/f
CL-V/f
OLV
CLV
AOLV
Configures the initial value of the cumulative drive operation time
in units of 10 hours.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the condition used to count the cumulative operation time.
0 : Logs power-on time
1 : Running Time
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value from which to start the cumulative drive cooling fan
operation time in 10-hour units.
V/f
CL-V/f
OLV
CLV
AOLV
U4-05 [CapacitorMaintenance] monitor values can be overwritten.
10.13 o: Keypad-Related Settings
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
Ref.
(Range)
0
906
(0 - 3)
0
906
(0, 1)
0
906
(0 - 3)
0
907
(0, 1)
1
907
(0, 1)
1
907
(0 - 3)
Default
Ref.
(Range)
0 h
908
(0 - 9999 h)
0
908
(0, 1)
0 h
908
(0 - 9999 h)
0%
908
(0 - 150%)
487