YASKAWA GA700 Technical Manual page 475

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

No.
Name
(Hex.)
L8-38
Carrier Frequency
Reduction
(04EF)
L8-40
CarrierFreqReduct
Off DelayTime
(04F1)
L8-41
High Current
Alarm Selection
(04F2)
L8-51
STPo I Detection
Level
(0471)
L8-52
STPo Integration
Level
(0472)
L8-53
STPo Integration
Time
(0473)
L8-54
STPo Id Diff
Detection
(0474)
L8-55
InternalBraking
TransistorProtect
(045F)
L8-56
Stl Act Time
(047D)
L8-57
Stl Retry Count
(047E)
L8-90
STPo Detection
Level
(0175)
L8-93
LSo Detection
Time at Low Speed Sets the time before baseblock is executed after LSo [LSo Fault] is
(073C)
L8-94
LSo Detection
Level at Low
(073D)
Speed
L8-95
Average LSo Freq
at Low Speed
(077F)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Selects the operation of the carrier frequency reduction function.
The carrier frequency is reduced when the output current exceeds a
specific level.
0 : Disabled
1 : Enabled below 6 Hz
2 : Enabled for the EntireSpeedRange
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time (off delay time) taken for the automatically reduced
carrier frequency to return to the state before the reduction.
V/f
CL-V/f
OLV
CLV
AOLV
Triggers an HCA [Current Alarm] when the output current exceeds
150% of the drive rated current.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the STPo [Desynchronization Error] on the basis of the output
current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for STPo [Desynchronization Error] on the
basis of the ACR integral value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time until STPo is detected after the value of L8-51 [STPo I
Detection Level] is exceeded.
V/f
CL-V/f
OLV
CLV
AOLV
Enables or disables the Id deviation detection function for STPo
[Desynchronization Error].
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Enables or disables protection for the internal braking transistor.
0 : Disable
1 : Protection enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time that the acceleration stall prevention function can
continue to operate, after which the STPo [Desynchronization
Error] is detected.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of times the acceleration stall prevention function
can operate until speeds match, after which the STPo
"Desynchronization Error" is detected.
V/f
CL-V/f
OLV
CLV
AOLV
STPo [Desynchronization Error] is detected when the control fault
reaches the detection level of L8-90.
V/f
CL-V/f
OLV
CLV
AOLV
detected.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for LSo [LSo Fault] as a percentage of E1-
04 [Maximum Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the average count of LSo [LSo Fault] detections.
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
10.11 L: Protection Function
Default
Ref.
(Range)
Determined by A1-
870
02, C6-01, and o2-
04
(0 - 2)
Determined by A1-
871
02
(0.00 - 2.00 s)
0
871
(0, 1)
0.0%
871
(0.0 - 300.0%)
1.0
871
(0.1 - 2.0)
1.0 s
871
(1.0 - 10.0 s)
1
871
(0, 1)
1
872
(0, 1)
5000 ms
872
(100 - 5000 ms)
10 times
872
(1 to 10 times)
Determined by A1-
872
02
(0 to 5000 times)
1.0 s
873
(0.0 - 10.0 s)
3%
873
(0 - 10%)
10 times
873
(1 to 50 times)
10
475