YASKAWA GA700 Technical Manual page 766

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
20 to 2F: External fault
Setting
Function
20 to 2F
External fault
EFx [External fault (terminal S1)] is displayed on the keypad when external fault is input. The keypad will
display EFx where x is the number of the terminal (terminal Sx) to which the external fault signal is input. For
example, when an external fault signal is input to terminal S3, EF3 will be displayed on the keypad.
Select the value set in H1-xx from a combination of the following three conditions.
• Signal input method from peripheral devices
• External fault detection method
• Motor stopping method (operates after an external fault is detected)
The following table shows the relationship between the combination of conditions and the value set to H1-xx.
Signal input method
from peripheral devices
Setting
N.O.
20
x
21
-
22
x
23
-
24
x
25
-
26
x
27
-
28
x
29
-
2A
x
2B
-
2C
x
2D
-
2E
x
2F
-
*1
Determine whether fault detection for the input signal method is either N.O. (external fault when switched ON) or N.C. (external
fault when turned OFF).
*2
Decide whether detection for the fault detection method should be enabled only during run or always detected.
30: PID integral reset
Setting
Function
30
PID integral reset
Note:
Refer to "PID control block diagram" for details.
766
V/f
CL-V/f
OLV
Selects the drive operation that was active at the time the failure or fault was detected in the
external device connected to the drive from any of the patterns between 20 to 2F.
Table 11.48 Stopping Method upon Detection of External Fault
External fault detection
method
*1
Detection
N.C.
always
enabled
-
x
x
x
-
-
x
-
-
x
x
x
-
-
x
-
-
x
x
x
-
-
x
-
-
x
x
x
-
-
x
-
V/f
CL-V/f
OLV
Resets the value of the PID control integral to 0 while the terminal is ON, and holds the value.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
*2
Detection
Ramp to
during run
Stop (fault)
only
-
x
-
x
x
x
x
x
-
-
-
-
x
-
x
-
-
-
-
-
x
-
x
-
-
-
-
-
x
-
x
-
Description
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Stopping Method
Coast to
Fast Stop
Stop (fault)
(fault)
-
-
-
-
-
-
-
-
x
-
x
-
x
-
x
-
-
x
-
x
-
x
-
x
-
-
-
-
-
-
-
-
Continuous
Operation
(minor
fault)
-
-
-
-
-
-
-
-
-
-
-
-
x
x
x
x

Advertisement

Table of Contents
loading

Table of Contents