YASKAWA GA700 Technical Manual page 712

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.7 F: Options
*1
Parameters set when using the Closed Loop V/f Control method.
*2
Parameters to set an option card connected to CN5-B.
F1-01: Encoder 1 Pulse Count (PPR)
No.
Name
(Hex.)
F1-01
PG 1 Pulses Per
Revolution
(0380)
F1-02: PG Feedback Loss Selection
No.
Name
(Hex.)
F1-02
PG Feedback Loss
Selection
(0381)
PGo is detected when the drive does not detect output pulses from the encoder for an amount of time longer than
or equal to the value set in F1-14 [PG Open-Circuit Detection Time].
Note:
• Faults such as ov [DB Bus Overvoltage] and oC [Overcurrent] may occur depending on the motor speed and load conditions.
• When using Advanced Open Loop Vector Control, this is enabled when n4-72 = 1 [Encoder Option Select for Advanced Open Loop
Vector Control = With PG].
0 : Ramp to stop
The drive ramps the motor to stop according to the deceleration time. The terminal turns on when H2-xx = E
[MFDO Function Select = Fault] is set.
1 : Coast to stop
The drive shuts off output and the motor coasts to stop. The terminal turns on when H2-xx = E.
2 : Fast Stop (use C1-09)
The drive stops the motor using the deceleration time set in C1-09 [Fast Stop Time]. The terminal turns on when
H2-xx = E.
3 : Alarm only
PGo appears on the keypad, and operation continues. This setting is not normally used as the motor and machine
is protected from damage.
4 : No alarm display
Operation continues without the display of PGo on the keypad. This setting is not normally used as the motor and
machine is protected from damage.
F1-03: Operation Select at Overspeed
No.
Name
(Hex.)
F1-03
Operation Select at
Overspeed
(0382)
Detects oS when the motor speed exceeds the value set in F1-08 [Overspeed Detection Level] for an amount of
time longer than or equal to the value set in F1-09 [Overspeed Detection Delay Time].
0 : Ramp to stop
The drive ramps the motor to stop according to the deceleration time. The terminal turns on when H2-xx = E
[MFDO Function Select = Fault].
1 : Coast to stop
The drive shuts off output and the motor coasts to stop. The terminal turns on when H2-xx = E.
2 : Fast Stop (use C1-09)
The drive stops the motor using the deceleration time set in C1-09 [Fast Stop Time]. The terminal turns on when
H2-xx = E.
3 : Alarm only
712
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of output pulses per revolution of the encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the motor operation when PGo [PG Disconnect] is detected.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the motor operation when oS [Overspeed] is detected.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
600 ppr
(1 - 60000 ppr)
Default Setting
(Range)
1
(0 - 4)
Default Setting
(Range)
1
(0 - 3)