YASKAWA GA700 Technical Manual page 671

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

Note:
• The upper limit value changes according to the value set in E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference
Upper Limit]. Use the following formula to calculate the upper limit value.
Upper limit value = (E1-04) × (d2-01) / 100
• The value set to o1-03 [Keypad Display Selection] is changed to 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control Method
Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector Control].
• To set d1-01 to 1-step speed parameter in a multi-step speed operation, set b1-01 = 0 [Frequency Reference Selection 1 = Keypad].
d1-02: Reference 2
No.
Name
(Hex.)
d1-02
Reference 2
(0281)
RUN
Note:
• The upper limit is determined by E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit].
• The value set to o1-03 [Keypad Display Selection] is changed to 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [AOLV/PM, CLV/
PM].
• To set d1-02 to Multi-Step Speed 2, set all MFAI function selections [H3-02, H3-06, and H3-10] to any other value than 2 [Auxiliary
Frequency Reference 1]. If the status is the default setting, set H3-06 = F [Terminal A3 Function Selection = Through Mode].
d1-03: Reference 3
No.
Name
(Hex.)
d1-03
Reference 3
(0282)
RUN
Note:
• The upper limit is determined by E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit].
• The value set to o1-03 [Keypad Display Selection] is changed to 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control Method
Selection = AOLV/PM, CLV/PM].
• To set d1-03 to Multi-Step Speed 3, set all MFAI function selections [H3-02, H3-06, and H3-10] to any other value than 3 [Auxiliary
Frequency Reference 2].
d1-04: Reference 4
No.
Name
(Hex.)
d1-04
Reference 4
(0283)
RUN
Note:
• The upper limit is determined by E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit].
• The value set to o1-03 [Keypad Display Selection] is changed to 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [AOLV/PM, CLV/
PM].
• Parameter d1-04 sets the frequency reference of Multi-Step Speed 4.
d1-05: Reference 5
No.
Name
(Hex.)
d1-05
Reference 5
(0284)
RUN
Note:
• The upper limit is determined by E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit].
• The value set to o1-03 [Keypad Display Selection] is changed to 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control Method
Selection = AOLV/PM, CLV/PM].
• Parameter d1-05 sets the frequency reference of Multi-Step Speed 5.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the unit set in o1-03 [Keypad Display
Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the unit set in o1-03 [Keypad Display
Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the unit set in o1-03 [Keypad Display
Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the unit set in o1-03 [Keypad Display
Selection].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.5 d: Reference Settings
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
11
671