YASKAWA GA700 Technical Manual page 456

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.10 H: Terminal Functions
Setting
Function
1C
Motor 2 Selection
1D
During
Regeneration
1E
Restart Enabled
1F
Motor Overload
Alarm (oL1)
20
Drive Overheat
Pre-Alarm (oH)
21
EDM
22
Mechanical
Weakening
Detection
2F
Maintenance
Period
30
During Torque
Limit
31
During speed limit
32
During Spd Limit
inTorqueControl
33
Zero Servo
Complete
37
During Frequency
Output
38
Drive Enabled
39
Watt Hour Pulse
Output
456
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when motor 2 is selected.
ON : Motor 2 Selection
OFF : Motor 1 Selection
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the motor is regenerating.
ON : Motor is regenerating.
OFF : Motor is operating or stopped.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when a fault that can be restarted occurs and the Auto Restart
function is attempting to operate.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the electronic thermal protector value of the motor overload
protective function reaches at least 90% of the detection level.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the drive heatsink temperature reaches the level set with L8-
02 [Overheat Alarm Level].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on (safety stop state) when the safety circuit and safety diagnosis
circuit is not experiencing a failure and when both terminals H1-HC and H2-HC are off
(released).
ON : Safety stop state
OFF : Safety circuit fault or RUN/READY
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when mechanical weakening is detected.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when consumables reach the estimated maintenance period.
Provides notification of the maintenance period for the following items.
• IGBT
• Cooling fan
• Capacitor
• Soft charge bypass relay
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the torque reference reaches the torque limit configured with
L7 parameters, H3-02, H3-06, or H3-10 [Multi-Function Analog In].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the speed limit is active.
V/f
CL-V/f
OLV
CLV
AOLV
The motor accelerates in forward or reverse when torque control is enabled and the
torque reference externally input is disproportionate to the load. The output terminal
turns on when this speed is restricted to no higher than a constant speed and the motor
speed is at the speed limit. Stopped operation is excluded.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when positioning within the range defined by b9-02 [Zero Servo
Completion Width] completes after the input of the Zero-Servo command.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
This terminal turns on when the terminal allocated to H1-xx = 6A [Drive Enable] is
turned on.
V/f
CL-V/f
OLV
CLV
AOLV
Outputs the pulse that represents the watt hours.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Ref.
794
794
794
794
794
794
795
795
795
795
795
796
796
796
796