YASKAWA GA700 Technical Manual page 768

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
40: Forward Run Command (2-Wire Seq)
Setting
Function
40
Forward Run
Command (2-Wire
Seq)
ON : Forward Run
OFF : Run Stop
Note:
• When the both Forward run command and Reverse run command terminals have been turned ON, the drive detects EF [FWD/REV Run
Command Input Error] (minor fault), and the motor ramps to stop.
• The Forward run/Reverse run command is set to terminals S1 and S2 when the drive is initialized using a 2-wire sequence.
• Simultaneous use with H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)] is not possible.
41: Reverse Run Command (2-Wire Seq)
Setting
Function
41
Reverse Run
Command (2-Wire
Seq)
ON : Reverse Run
OFF : Run Stop
Note:
• When the both Forward run command and Reverse run command terminals have been turned ON, the drive detects EF [FWD/REV Run
Command Input Error] (minor fault), and the motor ramps to stop.
• The Reverse run command is set to terminal S2 when the drive is initialized using a 2-wire sequence.
• Simultaneous use with H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)] is not possible.
42: Run Command (2-Wire Sequence 2)
Setting
Function
42
Run Command (2-
Wire Sequence 2)
ON : Run
OFF : Stop
Note:
Run Command (2-Wire Sequence 2) cannot be used at the same time as Forward/Reverse Run Command (2-Wire Seq) [H1-xx = 40,
41].
43: FWD/REV Command (2-Wire Seq 2)
Setting
Function
43
FWD/REV
Command (2-Wire
Seq 2)
768
V/f
CL-V/f
OLV
CLV
AOLV
Inputs the Forward run command for 2-wire sequence 1. Use it paired with the Reverse Run
Command (2-Wire Seq) [H1-xx = 41].
Figure 11.80 2-Wire Sequence Wiring Example
V/f
CL-V/f
OLV
CLV
AOLV
Inputs the Reverse run command for 2-wire sequence 1. Use it paired with the Forward Run
Command (2-Wire Seq) [H1-xx = 40].
V/f
CL-V/f
OLV
CLV
AOLV
Inputs the Run command for 2-wire sequence 2. Use it paired with the FWD/REV Command (2-
Wire Seq 2) [H1-xx = 43].
V/f
CL-V/f
OLV
CLV
AOLV
Selects the direction of motor rotation for 2-wire sequence 2. Use it paired with the Run Command
(2-Wire Sequence 2) [H1-xx = 42].
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM

Advertisement

Table of Contents
loading

Table of Contents