2.14 Control Circuit Wiring
A - Terminal block (TB2-3)
B - Terminal block (TB2-2)
C - Terminal block (TB2-1)
The tightening torque for the terminal screws is displayed on the reverse side of the front cover.
Wire Gauges and Tightening Torques
Use the tables in this section to select the appropriate wires. Use shielded wire when wiring the control circuit
terminal block. For simpler and more reliable wiring, use crimp ferrules on the wire ends.
The tightening torque for the control circuit terminal is displayed on the reverse side of the front cover.
Terminal
S1-S8, SC, SN, SP
H1, H2, HC
RP, +V, -V, A1, A2, A3, AC
MP, FM, AM, AC
DM+, DM-
D+, D-, AC
MA, MB, MC, M1-M4, P1, C1,
P2, C2
Crimp Ferrule
Always attach an insulated sleeve when using crimp ferrules. Refer to the following table for the recommended
external dimensions of the crimp ferrule and the model number.
Use the CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT.
76
Figure 2.45 Control Circuit Terminal Arrangement
Figure 2.46 Tightening Torque Display
Table 2.23 Wire Gauges and Tightening Torques
Tightening
Screw
Recommended
Torque
Size
N∙m (lb∙in)
mm
0.5 to 0.6
M3
(4.4 - 5.3)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
D - Terminal block (TB1)
E - Terminal block (TB3)
F - Terminal block (TB4)
Bare Wire
Wire Range
Gauge
mm
2
(AWG)
2
(AWG)
• Stranded wire
0.2 to 1.0
0.75
(24 - 16)
(18)
• Solid wire
0.2 to 1.5
(24 - 16)
Crimp Ferrule
Recommended
Wire Range
Gauge
mm
2
(AWG)
mm
2
(AWG)
0.5
0.25 to 0.5
(20)
(24 - 20)