YASKAWA GA700 Technical Manual page 782

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
H2-26: Comparator 2 Monitor Selection
No.
Name
(Hex.)
H2-26
Comparator 2
Monitor Selection
(1546)
Note:
• The configurable monitor varies depending on the control method.
• Set this parameter to 000 or 031 to use in through mode. The terminal output level from the PLC via MEMOBUS/Modbus
communications or the communication option can be configured.
• Refer to H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator1 and Comparator 2] for more information on
the comparator function.
H2-27: Comparator 2 Lower Limit
No.
Name
(Hex.)
H2-27
Comparator 2 Lower
Limit
(1547)
Note:
Refer to H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator1 and Comparator 2] for more information on
the comparator function.
H2-28: Comparator 2 Upper Limit
No.
Name
(Hex.)
H2-28
Comparator 2 Upper
Limit
(1548)
Note:
Refer to H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator1 and Comparator 2] for more information on
the comparator function.
H2-29: Comparator 2 Hysteresis
No.
Name
(Hex.)
H2-29
Comparator 2
Hysteresis
(1549)
Note:
Refer to H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator1 and Comparator 2] for more information on
the comparator function.
H2-30: Comparator 2 On-Delay Time
No.
Name
(Hex.)
H2-30
Comparator 2 On-
Delay Time
(154A)
Note:
Refer to H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator1 and Comparator 2] for more information on
the comparator function.
782
V/f
CL-V/f
OLV
CLV
AOLV
Configures the monitor number for comparator 2. Configure the x-xx
portion of Ux-xx [Monitor]. For example, to monitor U1-03 [Output
Current], set a value of 103.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the lower limit detection level for comparator 2 on the basis that
the full scale analog output for the monitor number selected with H2-26
[Comparator 2 Monitor Selection] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the upper limit detection level for comparator 2 on the basis that
the full scale analog output for the monitor number selected with H2-26
[Comparator 2 Monitor Selection] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the hysteresis level for comparator 2 on the basis that the full
scale analog output for the monitor number selected with H2-26
[Comparator 2 Monitor Selection] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the time for the monitor number configured with H2-26
[Comparator 2 Monitor Selection].
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default Setting
(Range)
103
(000 - 999)
Default Setting
(Range)
0.0%
(0.0 - 300.0%)
Default Setting
(Range)
0.0%
(0.0 - 300.0%)
Default Setting
(Range)
0.0%
(0.0 - 10.0%)
Default Setting
(Range)
0.0 s
(0.0 - 6000.0 s)