YASKAWA GA700 Technical Manual page 508

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.17 U: Monitors
No.
Name
(Hex.)
U6-07
q-Axis ACR
Output
(005F)
U6-08
d-Axis ACR
Output
(0060)
U6-09
AdvPhase Compen
Δθ
(07C0)
U6-10
ContAxisDeviation
Δθ
(07C1)
U6-13
FluxPosDetect
sensor
(07CA)
U6-14
FluxPosEstimOb
server
(07CB)
U6-17
Total Current Value
for Detection of
(07D1)
Direction of Motor
Rotation
U6-18
SpdDetectPG1
Counter
(07CD)
U6-19
SpdDetectPG2
Counter
(07E5)
U6-20
Frequency Ref
Bias (Up/Down 2) Displays the bias value used to adjust the frequency reference.
(07D4)
U6-21
Offset Frequency
(07D5)
U6-22
ZeroServoPulse
Move
(0062)
U6-25
Fdbk Control
Output
(006B)
U6-26
Feed Fwd Cont
Output
(006C)
508
Description
V/f
CL-V/f
OLV
CLV
AOLV
Displays the output value for current control relative to motor
secondary current. (q axis)
Unit: 0.1%
V/f
CL-V/f
OLV
CLV
AOLV
Displays the output value for current control relative to motor
excitation current. (d axis)
Unit: 0.1%
V/f
CL-V/f
OLV
CLV
AOLV
Displays the data on forward phase compensation for the calculation
results of the amount of control axis deviation.
Unit: 1 °
V/f
CL-V/f
OLV
CLV
AOLV
Displays the amount of deviation between the γδ-Axis used for
motor control and the actual dq-Axis.
Unit: 0.1 °
V/f
CL-V/f
OLV
CLV
AOLV
Displays the value of the flux position detection.
Unit: 0.1 °
V/f
CL-V/f
OLV
CLV
AOLV
Displays the value of the flux position estimation.
Unit: 0.1 °
V/f
CL-V/f
OLV
CLV
AOLV
Displays the accumulated time of direction of motor rotation
detections for Speed Estimation Speed Searches. This is used to
adjust the value of b3-26 [Direction Determining Level].
Note:
Upper and lower limits are set to values of ±32767.
V/f
CL-V/f
OLV
CLV
AOLV
Displays the number of pulses for speed detection (PG1).
Unit: 1 pulse
V/f
CL-V/f
OLV
CLV
AOLV
Displays the number of pulses for speed detection (PG2).
Unit: 1 pulse
V/f
CL-V/f
OLV
CLV
AOLV
Unit: 0.1%
V/f
CL-V/f
OLV
CLV
AOLV
Displays the total value of d7-01 to d7-03 [Offset Frequency 1 to 3]
selected with Offset frequency 1 to 3 [H1-xx = 44 to 46].
Unit: 0.1%
V/f
CL-V/f
OLV
CLV
AOLV
Displays how far the rotor has moved from its last position when
Zero Servo is available. Displays a number that is 4 times the
number of PG pulses.
Unit: 1 pulse
V/f
CL-V/f
OLV
CLV
AOLV
Displays the primary delay filter input value of the ASR (speed
control loop).
Unit: 0.01%
V/f
CL-V/f
OLV
CLV
AOLV
Displays the Feed Forward control output.
Unit: 0.01%
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
MFAO Signal
Ref.
Level
200 V class: 10 V
-
= 200 Vrms
400 V class: 10 V
= 400 Vrms
(-10 V to +10 V)
200 V class: 10 V
-
= 200 Vrms
400 V class: 10 V
= 400 Vrms
(-10 V to +10 V)
10 V: 180° (-10 V
-
to +10 V)
10 V: 180° (-10 V
-
to +10 V)
10 V: 180° (-10 V
-
to +10 V)
10 V: 180° (-10 V
-
to +10 V)
No signal output
-
available
10 V: 65536
-
10 V: 65536
-
10 V: Maximum
-
Frequency
10 V: Maximum
-
Frequency
10 V: Number of
-
pulses per
revolution (-10 V
to +10 V)
10 V: Motor
-
secondary rated
current (-10 V to
+10 V)
10 V: Motor
-
secondary rated
current (-10 V to
+10 V)

Advertisement

Table of Contents
loading

Table of Contents