YASKAWA GA700 Technical Manual page 741

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

1 : 10 kbps
2 : 20 kbps
3 : 50 kbps
4 : 125 kbps
5 : 250 kbps
6 : 500 kbps
7 : 800 kbps
8 : 1 Mbps
F6-45: BACnet Node Address
No.
Name
(Hex.)
F6-45
BACnet Node
Address
(02FB)
F6-46: BACnet Baud Rate
No.
Name
(Hex.)
F6-46
BACnet Baud Rate
(02FC)
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
F6-47: Rx to Tx Wait Time
No.
Name
(Hex.)
F6-47
Rx to Tx Wait Time
(02FD)
F6-48: BACnet Device Object Identifier0
No.
Name
(Hex.)
F6-48
BACnet Device
Object Identifier0
(02FE)
F6-49: BACnet Device Object Identifier1
No.
Name
(Hex.)
F6-49
BACnet Device
Object Identifier1
(02FF)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node address for BACnet communication.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the BACnet communications speed.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the wait time for reception and transmission of BACnet
communication.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the last word of addresses for BACnet communication.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the last word of addresses for BACnet communication.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.7 F: Options
Default Setting
(Range)
1
(0 - 127)
Default Setting
(Range)
3
(0 - 8)
Default Setting
(Range)
5 ms
(5 - 65 ms)
Default Setting
(Range)
0
(0 - FFFF)
Default Setting
(Range)
0
(0 - 3F)
11
741