4.2 European Standards
A - Grounding surface (Remove the
paint.)
B - Control panel
C - Metal plate
D - Drive
E - Ground the shield.
5.
Connect the DC reactor to prevent harmonic distortion.
selection.
Note:
• Install the DC reactor for drive models 2004, 2006, 4002, 4004 to maintain compliance with IEC/EN 61000-3-2.
• The main circuit terminal block for the drive, and the terminal blocks for the DC reactors come in different shapes. The drive
comes with a European style terminal block, and the DC reactors come with a round terminal block. Take due care when
preparing the ends of the wires.
Ground Wiring
WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply
could cause death or serious injury.
WARNING! Electrical Shock Hazard. For the drive (model: 2xxxA, 4xxxA) to comply with the EMC Directive, be sure to ground
its power supply with a neutral network. When your drive is not grounded with the neutral network or when it is grounded with a
high resistance network, it may cause electrical shock.
200
Figure 4.12 EMC Noise Filter and Drive Installation Procedure
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
F - Motor
G - Motor cable (Braided shield
cable: max. 10 m (32.8 ft.))
H - Cable clamp
I - Grounding wire
J - EMC noise filter
Refer to DC Reactor on page 202
for DC reactor