YASKAWA GA700 Technical Manual page 499

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

No.
Name
(Hex.)
U2-03
FreqRef at Pre
Fault
(0082)
U2-04
OutFreq at Pre
Fault
(0083)
U2-05
OutCurr at Pre
Fault
(0084)
U2-06
MotorSpd at
PreFault
(0085)
U2-07
OutVolt at Pre
Fault
(0086)
U2-08
DCBusVolt
atPreFault
(0087)
U2-09
Out Pow at Pre
Fault
(0088)
U2-10
Torque Ref at
Previous Fault
(0089)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Displays the frequency reference at the latest fault.
The current frequency reference can be monitored by U1-01 [Freq
Reference].
Unit: 0.01 Hz
V/f
CL-V/f
OLV
CLV
AOLV
Displays the output frequency at the latest fault.
The current output frequency can be monitored by U1-02 [Output
Frequency].
Unit: 0.01 Hz
V/f
CL-V/f
OLV
CLV
AOLV
Displays the output current at the latest fault.
The current output current can be monitored by U1-03 [Output
Current]. The value of U1-03 is displayed in ampere (A) on the
keypad.
When viewing via MEMOBUS/Modbus communications, the
current is "8192 = drive rated current (A)." Current can be calculated
from the monitor value present at MEMOBUS/Modbus
communications using "Numerals being displayed / 8192 × drive
rated current (A)."
Unit: Determined by the drive model.
• Models 2004 to 2042, 4002 to 4023: 0.01 A
• Models 2056 to 2415, 4031 to 4726: 0.1 A
V/f
CL-V/f
OLV
CLV
AOLV
Displays the motor speed at the latest fault.
The current motor speed can be monitored by U1-05 [Motor Speed].
Unit: 0.01 Hz
V/f
CL-V/f
OLV
CLV
AOLV
Displays the output voltage reference at the latest fault.
The current output voltage reference can be monitored by U1-06
[OutVoltage Reference].
Unit: 0.1 V
V/f
CL-V/f
OLV
CLV
AOLV
Displays the DC bus voltage at the latest fault.
The current DC bus voltage can be monitored by U1-07 [DC Bus
Voltage].
Unit: 1 V
V/f
CL-V/f
OLV
CLV
AOLV
Displays the output power at the latest fault.
The current output power can be monitored by U1-08 [Output
Power].
Unit: 0.1 kW
V/f
CL-V/f
OLV
CLV
AOLV
Displays the torque reference at the latest fault as a percentage of
the motor rated torque.
The current torque reference can be monitored by U1-09 [Torque
Reference].
Unit: 0.1%
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
10.17 U: Monitors
MFAO Signal
Ref.
Level
No signal output
-
available
No signal output
-
available
No signal output
-
available
No signal output
-
available
No signal output
-
available
No signal output
-
available
No signal output
-
available
No signal output
-
available
499
10

Advertisement

Table of Contents
loading

Table of Contents