11.10 n: Special Adjustment
n7-07: PLL response 1
No.
Name
(Hex.)
n7-07
PLL response 1
(3117)
n7-08: PLL response 2
No.
Name
(Hex.)
n7-08
PLL response 2
(3118)
Note:
When the setting value is increased, a speed search of a motor rotating at a high frequency can be performed. However, if the setting
value is too high, the calculated speed will oscillate and a restart will fail. In such cases reduce the setting value.
n7-10: Sensorless Switchover StartSpeed
No.
Name
(Hex.)
n7-10
Sensorless
Switchover
(311A)
StartSpeed
Note:
• The value set in n8-51 [Accel / Decel Pull-In Current] is enabled with speeds that do not exceed the value set in n7-10. The value set in
b8-01 [Energy Saving Control Selection] is enabled with speeds higher than the value set in n7-10.
• If a significant amount of oscillation occurs when running at low-speeds, increase the setting value.
• Reduce the setting value when priority is to be placed on energy-saving measures in the low speed range.
n7-17: Resistance TemperatureCorrection
No.
Name
(Hex.)
n7-17
Resistance
TemperatureCorrec
(3122)
tion
0 : Invalid
1 : Valid (Only 1 time)
2 : Valid (Every time)
Note:
• With the settings n7-17 = 1, 2, there could be some delay before startup because of the adjustment time.
• With the settings n7-17 = 1, 2, the line-to-line resistance value of E9-10 [Motor Line-to-Line Resistance] may be set.
• Set n7-17 = 2 if the temperature state is likely to change at startup.
• To shorten the startup time, set n7-17 = 0, then perform line-to-line resistance tuning.
• If startup from the coasting state can be expected, set n7-17 = 0, then perform line-to-line resistance tuning.

n8: PM Motor Control Tuning

n8 parameters are used to make adjustments when controlling PM motors.
n8-01: Init Rotor Position Est Current
No.
Name
(Hex.)
n8-01
Init Rotor Position
Est Current
(0540)
888
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed calculation gain during normal operation. Normally there is
no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed calculation gain during a speed search.
V/f
CL-V/f
OLV
CLV
AOLV
The speed range within which pull-in current commands are enabled is set
as a proportion relative to the rated frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the function for compensating for changes in the motor resistance
value caused by temperature fluctuations.
V/f
CL-V/f
OLV
CLV
AOLV
Sets, as a percentage, the Initial Rotor Position Estimated Current, taking
the E5-03 [Motor Rated Current (FLA)] as the 100% value. Normally there
is no need to change this setting.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default Setting
(Range)
15.0 Hz
(1.0 - 50.0 Hz)
Default Setting
(Range)
25.0 Hz
(1.0 - 50.0 Hz)
Default Setting
(Range)
10.0%
(0.0 - 100.0%)
Default Setting
(Range)
1
(0 - 2)
Default
(Range)
50%
(0 - 100%)