Sets whether to execute Auto restart and the number of attempts to perform within a set time. Drive output is shut
off and operation stops if the number of Auto Restart attempts exceeds the set value during the set time. In such
cases, resolve the cause of the fault and manually restart the drive.
DANGER! Sudden Movement Hazard. Never use the fault restart function so that the drive restarts the application after a fault
occurs in hoist or lifting applications. Failure to comply may result in death or serious injury.
The drive can execute the Auto Restart function when the following faults occur.
Fault
GF
LF
oC
oH1
oL1
oL2
oL3
oL4
*1
Uv1 is the target for the fault retry process when configured such that L2-01 = 1, 2, 3, or 4 [Momentary Power Loss Ope Select=
Enbl with Timer, Enbl whl CPU act, KEB Mode, or KEB Stop Mode].
L5-01: Number of Auto Restart Attempts
No.
Name
(Hex.)
L5-01
Number of Auto
Restart Attempts
(049E)
The number of Auto Restart attempts is reset to 0 in the following situations.
• The drive operates normally for 10 minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.
L5-02: AutoRestartFaultOutputOpeSelect
No.
Name
(Hex.)
L5-02
AutoRestartFaultOut
putOpeSelect
(049F)
0 : Fault output not active
1 : Fault output active
L5-04: Auto Restart Interval Time
No.
Name
(Hex.)
L5-04
Auto Restart Interval
Time
(046C)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Table 11.58 List of Faults during which Auto Restart is Available
Name
Ground Fault
Output Phase Loss
Overcurrent
Overheat 1 (Heatsink Overheat)
Motor Overload
Drive Overloaded
Overtorque Detection 1
Overtorque Detection 2
V/f
CL-V/f
OLV
CLV
Sets the number of that can be automatically performed by the drive.Sets the
number of Auto Restart operations that the drive may attempt to restart
itself.
V/f
CL-V/f
OLV
CLV
Selects whether to output signals to the MFDO terminal set for Fault [H2-
xx = E] while the drive is executing Auto restart.
V/f
CL-V/f
OLV
CLV
Sets the time interval between each Auto Restart process. This function is
enabled when L5-05 = 1 [Auto Restart Operation Selection = Use L5-04
Time].
Fault
ov
PF
rH
rr
Uv1
STPo
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.9 L: Protection Function
Name
DC Bus Overvoltage
Input Phase Loss
Mounted Braking Resistor
Overheating
Dynamic Braking Transistor
Undervoltage
*1
Pull-Out Detection
Default
(Range)
0
(0 - 10 times)
Default
(Range)
0
(0, 1)
Default
(Range)
10.0 s
(0.5 - 600.0 s)
11