F6: Communication Option and Ethernet Option

No.
Name
(Hex.)
F6-01
Communication
Error Selection
(03A2)
F6-02
Comm External
Fault (EF0) Detect Selects the conditions at which EF0 [Option Card External Fault] is
(03A3)
F6-03
Comm External
Fault (EF0) Select
(03A4)
F6-04
bUS Error
Detection Time
(03A5)
F6-06
Torque Reference/
Limit by Comm
(03A7)
F6-07
MultiStep Ref
Priority Select
(03A8)
F6-08
Comm Parameter
Reset @Initialize
(036A)
F6-10
CC-Link Node
Address
(03B6)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Selects the operation of the drive when bUS [Option
Communication Error] is detected.
0 : Ramp to stop
1 : Coast to stop
2 : Fast Stop (use C1-09)
3 : Alarm only
4 : Alarm - run at d1-04
5 : Alarm - Ramp Stop
V/f
CL-V/f
OLV
CLV
AOLV
detected.
0 : Always detected
1 : Detection during run only
V/f
CL-V/f
OLV
CLV
AOLV
Selects the operation of the drive when EF0 [Option Card External
Fault] is detected.
0 : Ramp to stop
1 : Coast to stop
2 : Fast Stop (use C1-09)
3 : Alarm only
V/f
CL-V/f
OLV
CLV
AOLV
Sets the delay time until bUS [Option Communication Error] issues
are detected.
Note:
The setting value changes to 0.0 s when the option card is
mounted in the drive.
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether to enable or disable the torque reference and torque
limit received from the communication option card.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether to enable/disable the multi-step speed reference
when NetRef (communication option card) or ComRef
(MEMOBUS/Modbus communications) is selected as the frequency
reference source.
0 : MultiStep References Disabled
1 : MultiStep References Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether or not to initialize communication parameters [F6-
xx and F7-xx] when the drive is initialized by A1-03 [Initialize
Parameters].
0 : No Reset - parameters retained
1 : Reset - back to factory default
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node address for CC-Link communication. The drive must
be restarted when the setting is changed.
Note:
Set a node address that does overlap with other nodes. Do not set
this parameter to a value of 0. If the parameter is set incorrectly,
the L.ERR LED on the option is lit, and the drive will detect the
AEr [Node Address Setting Error] error.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
10.9 F: Options
Default
Ref.
(Range)
1
732
(0 - 5)
0
732
(0, 1)
1
732
(0 - 3)
2.0 s
733
(0.0 - 5.0 s)
0
733
(0, 1)
0
733
(0, 1)
0
733
(0, 1)
0
733
(0 - 64)
435
10