7.5

Replace the Drive

About the Control Circuit Terminal Block

The control circuit terminal block of this product can be attached and detached. The control circuit terminal block
can be easily replaced if the drive fails to operate correctly.
A - Control circuit terminal block

Replace the Drive

WARNING! Electrical Shock Hazard. While the drive is ON, never attempt to change any wiring, disconnect any option cards or
connectors, or replace the cooling fan. Before performing any repairs, shut OFF the power supply to the drive and verify that
there is no residual voltage in the unit. Failure to do so may result in serious electric shock.
WARNING! Electrical Shock Hazard. Only authorized persons qualified in electrical work should perform installation, wiring,
maintenance, inspections, parts replacement, and repairs. Failure to comply may cause electrical shock.
WARNING! Electrical Shock Hazard. Do not perform inspections or wiring while the drive is energized. De-energize all devices
before carrying out any wiring or repair operations. Voltage will remain within the capacitors inside the drive even after the
power has been switched off. The Charge LED is extinguished once the DC bus voltage goes below 50 V DC. To prevent
electric shock, always wait for at least the amount of time indicated on the warning labels and confirm that all indicators are
OFF. Then, remove the front cover and terminal cover, measure the input power supply voltage and the DC bus voltage, and
make sure that the voltages have been lowered to safe levels. Failure to comply may result in death or serious injury.
NOTICE: Observe proper electrostatic discharge (ESD) procedures when handling the drive and circuit boards. Failure to
comply could cause ESD damage to the drive circuitry.
Remove the Control Circuit Terminal Block
First remove the keypad and front cover.
1.
Loosen the screws on the control circuit terminal block.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
B - Control circuit terminal block
fastening screw
Figure 7.17 Control Circuit Terminal Block
Figure 7.18 Loosen Fastening Screws
7.5 Replace the Drive
349