11.8 H: Terminal Functions

11.8
H: Terminal Functions
H parameters are used to assign functions to external input and output terminals.

H1: Multi-function digital input

H1 Parameters set the MFDI terminal functions.
H1-01 to H1-08 Terminal S1 to S8 Function Select
The drive has eight MFDI terminals. Refer to the following table for drive default settings and functions.
No.
H1-01
H1-02
H1-03
H1-04
H1-05
H1-06
H1-07
H1-08
*1
The value in parentheses indicate the default setting when initialized with A1-03 = 3330 [Initialize Parameters = 3-Wire
initialization].
Refer to the following table and use H1-xx [MFDI Function Select] to set the function.
Setting
0
3-Wire Sequence
*1
1
LOCAL/REMOTE Selection
2
External Reference 1/2 Selection
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time Selection 1
8
Baseblock Command (N.O.)
*1
9
Baseblock Command (N.C.)
*1
A
Accel/Decel Ramp Hold
B
oH2 [Drive Overheat Warning]
C
Analog Terminal Input Selection
D
PG Encoder Disable
E
ASR Integral Reset
F
Through Mode
10
Up Command
11
Down Command
12
Forward Jog
*1
13
Reverse Jog
*1
14
Fault Reset
752
Name
Terminal S1 Function Selection
Terminal S2 Function Selection
Terminal S3 Function Selection
Terminal S4 Function Selection
Terminal S5 Function Selection
Terminal S6 Function Selection
Terminal S7 Function Selection
Terminal S8 Function Selection
Table 11.45 Multi-Function Digital Input Setting Values
Function
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Default Setting
40(F)
*1
41(F)
*1
24
14
3(0)
*1
4(3)
*1
6(4)
*1
8
Setting
15
Fast Stop (N.O.)
*1
16
Motor 2 Selection
17
Fast Stop (N.C.)
*1
18
Timer Function Input
19
PID Disable
1A
Accel/Decel Time Selection 2
1B
Program Lockout
1E
Reference Sample Hold
20 through 2F
External Fault
*1
30
PID Integral Reset
31
PID Integral Hold
32
Multi-Step Speed Reference 4
34
PID Soft Starter Cancel
35
PID Input Level Selection
3E
PID Setpoint Selection 1
3F
PID Setpoint Selection 2
40
Forward Run Command (2-Wire Seq)
*1
41
Reverse Run Command (2-Wire Seq)
*1
42
Run Command (2-Wire Sequence 2)
*1
43
FWD/REV Command (2-Wire Seq 2)
*1
44
Offset Frequency 1
Function
Forward Run Command (2-Wire
Seq)
Reverse Run Command (2-Wire
Seq)
External fault (N.O., detection
always enabled, coast to stop)
Fault Reset
Multi-Step Speed Reference 1
Multi-Step Speed Reference 2
Jog Reference Selection
Baseblock Command (N.O.)
Function