11.8 H: Terminal Functions
2 : Terminal A2 only
3 : Terminals A1 and A2 only
4 : Terminal A3 only
5 : Terminals A1 and A3
6 : Terminals A2 and A3
7 : All terminals enabled
Note:
• Only the analog input terminal selected with H3-14 is affected by the ON/OFF operation of the terminal Sx as set with Analog
Terminal Input Selection [H1-xx = C].
• When not H1-xx = C, the functions set to terminals A1 to A3 will be enabled all of the time.
H3-16: Terminal A1 Offset
No.
Name
(Hex.)
H3-16
Terminal A1 Offset
(02F0)
Adds the offset value for the analog input value. For voltage input, sets the offset when a signal of 0 V is input.
For current input, sets the offset when a signal of 4 mA [H3-01= 2] or 0 mA [H3-01 = 3] is input.
H3-17: Terminal A2 Offset
No.
Name
(Hex.)
H3-17
Terminal A2 Offset
(02F1)
Adds the offset value for the analog input value. For voltage input, sets the offset when a signal of 0 V is input.
For current input, sets the offset when a signal of 4 mA [H3-09 = 2] or 0 mA [H3-09 = 3] is input.
H3-18: Terminal A3 Offset
No.
Name
(Hex.)
H3-18
Terminal A3 Offset
(02F2)
Adds the offset value for the analog input value. For voltage input, sets the offset when a signal of 0 V is input.
For current input, sets the offset when a signal of 4 mA [H3-05 = 2] or 0 mA [H3-05 = 3] is input.
H3-40: Extend MFAI1 Function Selection
No.
Name
(Hex.)
H3-40
Extend MFAI1
Function Selection
(0B5C)
The MFAI function can be used from the MEMOBUS/Modbus communications. Sets the desired function in H3-
40. Sets the input for the function in MEMOBUS/Modbus register 15C1. Refer to H3-xx "MFAI Setting Values"
for the setting values.
H3-41: Extend MFAI2 Function Selection
No.
Name
(Hex.)
H3-41
Extend MFAI2
Function Selection
(0B5F)
Refer to H3-xx "MFAI Setting Values" for the setting values.
806
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for the analog signal input to terminal A1. Normally
there is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A2. Normally there
is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A3. Normally there
is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the MEMOBUS AI1 function.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the MEMOBUS AI2 function.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default Setting
(Range)
0
(-500 - +500)
Default Setting
(Range)
0
(-500 - +500)
Default Setting
(Range)
0
(-500 - +500)
Default Setting
(Range)
F
(4 - 2F)
Default Setting
(Range)
F
(4 - 2F)