YASKAWA GA700 Technical Manual page 193

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

CE Standards Compliance for DC Power Supply Input
Install a fuse to the DC power supply input to comply with CE Standards.
Figure 4.3
shows a wiring example for using a DC power supply with two drives connected in parallel.
Note:
• Install a fuse to the DC power supply input for each drive when connecting multiple drives in parallel. Replace all fuses if any of the
fuses blow.
• Use an external EMC filter and make sure if the system comply with the EMC Directive.
• Do not connect the DC bus line to the ground.
Refer to
Table 4.6
and
Table 4.7
Three-Phase 200 V Class
Drive Model
2004
2006
2008
2010
2012
2018
2021
2030
2042
2056
2070
2082
2110
2138
*2
2169
*2
2211
*2
2257
*2
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Figure 4.3 Wiring Example for DC Power Input
for the recommended fuses and fuse holders.
Table 4.6 Recommended Fuse (Three-Phase 200 V Class)
Model
FWH-45B
FWH-45B
FWH-45B
FWH-45B
FWH-50B
FWH-80B
FWH-80B
FWH-125B
FWH-150B
FWH-200B
FWH-250A
FWH-250A
FWH-300A
FWH-250A
FWH-275A
FWH-300A
FWH-350A
FWH-350A
FWH-450A
FWH-450A
FWH-600A
FWH-600A
FWH-700A
Fuse
Manufacturer: Bussmann
*1
*1
*1
*1
*1
*1
4.2 European Standards
Qty
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
193