H5: Memobus/Modbus Communication - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
H4-07: MFAO Term FM Signal Level Select
No.
Name
(Hex.)
H4-07
Terminal FM Signal
Level Select
(0423)
Note:
Set jumper S5 on the control circuit terminal block accordingly when changing these parameters.
0 : 0-10 VDC
1 : -10 +10 VDC
2 : 4-20 mA
H4-08: MFAO Term AM Signal Level Select
No.
Name
(Hex.)
H4-08
Terminal AM Signal
Level Select
(0424)
Note:
Set jumper S5 on the control circuit terminal block accordingly when changing these parameters.
0 : 0-10 VDC
1 : -10 +10 VDC
2 : 4-20 mA
H4-20: Output Power Monitor Level
No.
Name
(Hex.)
H4-20
Output power
monitor level
(0B53)
Note:
• When H4-20 = 0.00 kW, the output power monitor 10 V level = motor rated power (kW). It is determined by the A1-02 [Control
Method Selection] setting.
–A1-02 = 0, 1 [V/f Control, Closed Loop V/f Control]: E2-11 [Motor Rated Power (kW)]
–A1-02 = 2, 3, 4 [Open Loop Vector Control, Closed Loop Vector Control, Advanced OpenLoop Vector Control]: E2-11 [Motor Rated
Power (kW)]
–A1-02 = 5, 6, 7 [PM Open Loop Vector Control, PM Advanced Open Loop Vector, PM Closed Loop Vector Control]: E5-02 [PM
Motor Rated Capacity]
–A1-02 = 8 [EZ Open Loop Vector Control]: E9-07 [Mtr Rated Power]

H5: Memobus/Modbus Communication

H5 parameters are used to configure the drive to use MEMOBUS/Modbus communications.
Serial communication with programmable controllers (PLC) can be performed using the MEMOBUS/Modbus
protocol over the RS-485 port (terminals D+ and D-) built into the drive.
H5-01: Drive Node Address
No.
Name
(Hex.)
H5-01
Drive Node Address
(0425)
Note:
• Restart the drive to enable the settings.
• Setting the parameter to 0 will cause the drive to stop responding to MEMOBUS/Modbus communications.
The drive must be configured with a slave address to enable the drive to communicate with the controller (master)
over MEMOBUS/Modbus communications. Set H5-01 to any value other than 0.
816
V/f
CL-V/f
OLV
CLV
AOLV
Selects the output signal level from the MFAO terminal FM.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the signal level output from the MFAO terminal AM.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level at 10 V when U1-08 [Output Power] executes analog output.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the communication slave address for drives.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0
(0 - 2)
Default
(Range)
0
(0 - 2)
Default Setting
(Range)
0.00 kW
(0.00 - 650.00 kW)
Default
(Range)
1FH
(0 - FFH)