D2: Reference Limits - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.5 d: Reference Settings
d1-15: Reference 15
No.
Name
(Hex.)
d1-15
Reference 15
(0290)
RUN
Note:
• The upper limit is determined by E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit].
• The value set to o1-03 [Keypad Display Selection] is changed to 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control Method
Selection = AOLV/PM, CLV/PM].
• Parameter d1-15 sets the frequency reference of Multi-Step Speed 15.
d1-16: Reference 16
No.
Name
(Hex.)
d1-16
Reference 16
(0291)
RUN
Note:
• The upper limit is determined by E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit].
• The value set to o1-03 [Keypad Display Selection] is changed to 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control Method
Selection = AOLV/PM, CLV/PM].
• Parameter d1-16 sets the frequency reference of Multi-Step Speed 16.
d1-17: Jog Reference
No.
Name
(Hex.)
d1-17
Jog Reference
(0292)
RUN
Note:
• The upper limit is determined by E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit].
• The value set to o1-03 [Keypad Display Selection] is changed to 1 [0.01% (100% = E1-04)] when A1-02 = 6, 7 [Control Method
Selection = AOLV/PM, CLV/PM].

d2: Reference Limits

d2 parameters set the upper and lower frequency limits to control the motor speed. Apply these parameters to for
example, run the motor at low-speed due to mechanical strength concerns, or if the motor should not be run at low
speed because of lubrication issues with the gears and bearings.
The upper frequency limit is set in d2-01 [Frequency Reference Upper Limit] and the lower limit is set in d2-02
[Frequency Reference Lower Limit].
674
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the unit set in o1-03 [Keypad Display
Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the unit set in o1-03 [Keypad Display
Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Jog frequency reference according to the units set in o1-03
[Frequency Display Unit Selection]. Set H1-xx = 6 [Terminal Sx Function
Selection = Jog Reference Selection] to use the Jog frequency reference.
Figure 11.58 Upper and Lower Frequency Limits
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
6.00 Hz
(0.00 - 590.00 Hz)