Dynamic Braking Option Overload Protection - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

2.17 Install Braking Resistor
Figure 2.63 Connect Braking Units in Parallel

Dynamic Braking Option Overload Protection

When using a dynamic braking option, Set up the sequence to shut off the power at the thermal relay trip contact
on the braking resistor unit as shown in the following figure to protect the braking resistor unit from overheating.
2
Figure 2.64 Power Supply Interrupt for Overheat Protection (Example)
WARNING! Fire Hazard. When using a braking unit, use a thermal relay on the braking resistors and configure a fault contact
output for the braking resistor unit to disconnect drive main power via an input contactor. Inadequate braking circuit protection
could result in death or serious injury by fire from overheating resistors.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
87