YASKAWA GA700 Technical Manual page 603

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

• 2-wire Sequence 2
This sequence allows for two types of input: Run/Stop and FWD/REV.
• 3-Wire Sequence
This sequence allows for three types of input: Run, Stop, and FWD/REV. Setting A1-03 = 3330 [Initialize
Parameters = 3-Wire initialization] and initializing the drive sets terminals S1, S2, and S5 for a 3-wire
sequence.
2 : Memobus/Modbus Communications
Enter the Run command by using MEMOBUS/Modbus communications, which comes standard with the drive.
3 : Option PCB
Use a communications option card or input option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card for installation and communications settings.
Note:
If b1-02 = 3 is set and an option card is not connected, then oPE05 [Run Cmd/Freq Ref Source Sel Err] will flash on the keypad.
b1-17: Run Command at Power Up
No.
Name
(Hex.)
b1-17
Run Command at
Power Up
(01C6)
0 : Disregard existing RUN command
The drive does not start operating the application when the power is switched ON, even if the Run command is
already enabled.
Re-enter the Run command to have the drive operate the application.
Note:
For safety, the drive is set so that it will not start operating the application when the power is switched ON, even if the Run command is
already enabled. The
the power is switched ON.
1 : Accept existing RUN command
The drive starts operating the application when the power is switched ON if the Run command is already enabled.
WARNING! Sudden Movement Hazard. When using a 3-Wire sequence, set the drive to 3-Wire sequence and set b1-17 = 0
[Run Command at Power Up = Disregard Existing RUN Command] before wiring the control terminals so the drive will not
accept a Run command at power up. The motor may rotate in reverse when the drive is powered up if the drive is wired for a 3-
wire sequence but set up for a 2-wire sequence (default) and b1-17 = 1 [Accept Existing RUN Command]. Failure to comply
could cause death or serious injury from moving equipment.
b1-21: CLV Start Selection
No.
Name
(Hex.)
b1-21
CLV Start Selection
(0748)
0 : Reject Run if b2-01< Nfdbk<E1-09
The Run command input is not accepted when the motor speed is at least the setting value of b2-01 or less than
the setting value of E1-09.
1 : Accept Run command at any speed
The Run command input is accepted when the motor speed is at least the setting value of b2-01 or less than the
setting value of E1-09.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
Selects what action to take when the power supply is switched ON and the
Run command is input from an external source. It is necessary to set this
parameter in applications where the Run command is already enabled when
the power supply switches ON/OFF.
light on the keypad will flash quickly if the Run command is already enabled from an external source when
V/f
CL-V/f
OLV
CLV
Selects the condition used to accept the Run command when A1-02 = 3 or 7
[Control Method Selection = Closed Loop Vector Control or PM Closed
Loop Vector Control]. Normally there is no need to change this setting.
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.3 b: Application
Default
(Range)
0
(0, 1)
Default Setting
(Range)
0
(0, 1)
11
603