YASKAWA GA700 Technical Manual page 763

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

Note:
• There is no need to input the Run command.
• The Reverse JOG command has priority over all other frequency references.
• The drive performs ramp to stop when the Forward JOG and Reverse JOG commands have been turned ON at the same time for 500
ms or more.
14: Fault Reset
Setting
Function
14
Fault Reset
When a fault is detected, the drive turns ON the fault relay output and shuts off the output. The motor coasts to
stop.
When a fault is detected for which the stopping method can be selected, apply the selected Stopping Method.
Then press the
(RESET) on the keypad to turn the Run command OFF, or reset the fault by setting the fault
reset terminal ON.
Note:
The fault reset signal is disregarded when the Run command is enabled. Remove the Run command before attempting to clear a fault
situation.
15: Fast Stop (N.O.)
Setting
Function
15
Fast Stop (N.O.)
The drive will not restart the motor after fast stop input has been canceled until the following conditions are met.
• The motor is completely stopped.
• The Run command is canceled.
• The fast stop command is canceled.
Note:
• Set 17 (Fast Stop (N.C.)) to input the emergency stop command using the N.C. switch.
• Refer to "C1-09: Fast Stop Time" for details.
NOTICE: Rapid deceleration can trigger an overvoltage fault. Set an appropriate Fast Stop time in C1-09 [Fast Stop Time] to
avoid this uncontrolled motor state and to ensure that the motor stops quickly and safely. The drive output shuts off when faulted
and the motor coasts.
16: Motor 2 Selection
Setting
Function
16
Motor 2 Selection
The user can switch between 2 induction motors using an external input, and operate them. The drive saves the
control methods, V/f patterns, and motor parameters of the 2 motors, and optimizes control of them both.
ON : Selects motor 2
OFF : Selects motor 1
If motor 2 is selected, the parameters used by the drive are switched to the motor 2 parameters.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal is ON while the Run command is inactive, the fault currently detected by the
drive will be reset.
V/f
CL-V/f
OLV
CLV
AOLV
When Fast Stop (N.O.) is input while the drive is running, the drive performs ramp to stop in a
deceleration time configured with C1-09 [Fast Stop Time].
V/f
CL-V/f
OLV
CLV
AOLV
Switches between motors 1 and 2. Switch between motors when they are stopped.
11.8 H: Terminal Functions
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11
763