Test Run

After using the Setup Wizard to make settings for the basic parameters, and Auto-Tuning of the motor has been
completed, the next step is to perform a test run.
WARNING! Crash Hazard. Conduct test operations to make sure that the drive operates safely after writing work is completed
and parameters have been set. Failure to comply may cause injury or damage to equipment.

No-Load Test Run

Before connecting the motor with machinery, check the operation status of the motor.
Precautions to Note before Operation
Before rotating the motor, check the following items.
• Make sure there are no issues related to safety around the motor and machinery.
• Ensure that all emergency stop circuits and machine safety mechanisms are functioning correctly.
Items to Check before Operation
Before operation check the following items:
• Is the motor rotating in the forward direction?
• Is the motor rotating smoothly (no abnormal sounds or abnormal vibrations)?
• Does the motor accelerate/decelerate smoothly?

Perform a No-Load Test Run

The basic steps to follow to perform a no-load test run are explained in the following.
1.
Energize the drive, or press
If [Home] is not displayed for
2.
Press
so the LOCAL/REMOTE indicator is lit.
3.
Press
to display d1-01 [Reference 1], and set to 6.00 Hz.
4.
Press
.
The RUN indicator lights, and the motor runs at 6.00 Hz in the forward direction.
5.
Confirm that the motor is rotating in the correct direction and that there are no faults indicated by the drive.
If any faults were detected, eliminate their cause.
A - Forward Rotation of Motor (Counter Clockwise Direction as Seen from
Load Shaft)
6.
Raise the frequency reference value by pressing
Change the setting value in increments of 10 Hz if needed while evaluating the response.
7.
Check the drive's output current using U1-03 [Output Current] each time the setting value is raised.
The status is normal if the output current of the drive does not exceed the motor rated current.
Ex.: 6 Hz → 20 Hz → 30 Hz → 40 Hz → 50 Hz → 60 Hz
8.
After confirming that the motor rotates normally, press
The RUN indicator will be flashing. Then, when the motor is completely stopped, it will go out.

Actual-Load Test Run

After testing operation without a load, connect the motor and machinery to perform a test run.
Precautions to Note before Operation
• Make sure there are no issues related to safety around the motor and machinery.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
(Home) to display the HOME screen.
, press
(Back), and then press
.
.

3.9 Test Run

to display (Home).
161