YASKAWA GA700 Technical Manual page 31

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

A - At least 50 mm (2 in.)
B - At least 30 mm (1.2 in.) on both
sides
Note:
• If the dimensions of the drives differ when using a side-by-side installation, then line up the tops of all the drives. This makes it easier
to replace the cooling fan later.
• If mounting an enclosed wall-mounted type (UL Type 1) drive using a side-by-side installation, completely remove the top protective
cover for the drive. Refer to "Attach the Top Protective Cover" to remove the top protective cover.
Figure 2.4 Enclosed Wall-Mounted Type (UL Type 1) Side-by-Side Mounting
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Figure 2.3 Drive Installation Space (Side-by-Side Mounting)
2.3 Installation Orientation and Spacing
C - At least 2 mm (0.08 in.) between
each drive
D - At least 120 mm (4.7 in.) above
and below
2
31