YASKAWA GA700 Technical Manual page 321

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

Code
Name
rdEr
Error Reading Data
Code
Name
vAEr
Voltage Class, Capacity
Mismatch
Code
Name
vFyE
VERIFY ERROR
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
6.8 Backup Function Operating Mode Display and Errors
Cause
Backup was executed with o3-02 = 0
[Copy Allowed Selection = Disabled]
set.
Cause
The power supply specifications or
drive capacity parameter settings differ
between the keypad and the drive.
Cause
Indicates that the parameters backed up
in the keypad and the parameters in the
drive do not match.
Possible Solution
Set o3-02 = 1 [Enabled] and execute backup again.
Possible Solution
1. Make the drive model and the value set in o2-
04 [Drive Model Selection] match.
2. Restore the parameter again.
Possible Solution
1. Restore or backup the parameter again.
2. Verify the parameter again.
6