11.11 o: Keypad-Related Settings
The
is still enabled when the Run command source has not been assigned to the keypad.
When restarting the drive after pressing the
on again.
o2-03: User Parameter Default Value
No.
Name
(Hex.)
o2-03
User Parameter
Default Value
(0507)
When o2-03 = 1 [Set defaults], changed parameter settings are saved as user parameter setting values in a region
of memory separate from drive parameters.
When initialization is performed while A1-03 = 1110 [Initialize Parameters = User initialization], the internal
drive parameter setting values are reset to the user parameter setting values that are saved when o2-03 = 1.
0 : No change
1 : Set defaults
Stores changed parameter setting values as user default settings.
When o2-03 = 1, pressing the
has been stored, o2-03 automatically resets to 0.
2 : Clear all
When o2-03 = 1, the stored user parameter setting values are cleared.
When o2-03 = 2, pressing the
automatically reset to 0. If user parameter setting values have been cleared, parameter initialization with a
configuration of A1-03 = 1110 cannot be executed.
o2-04: Drive Model Selection
No.
Name
(Hex.)
o2-04
Drive Model
Selection
(0508)
NOTICE: If o2-04 [Drive Model Selection] is not configured correctly, this will not only degrade performance, but this may also
result in the protection function not operating correctly, which could lead to the drive becoming damaged.
Note:
When the setting value of o2-04 is changed, related parameter setting values are also changed. Refer to "Parameters Changed from
Default Values with o2-04 [Drive Model Selection]" for more information.
o2-05: Freq Ref Setting Method Select
No.
Name
(Hex.)
o2-05
Freq Ref Setting
Method Select
(0509)
0 : Disabled
The
must be pressed to enable the frequency reference value changed with the keypad.
1 : Enabled
The frequency reference is changed as soon as it is entered with the keypad, which then changes the output
frequency. Thus, the
frequency reference value is changed using the
904
V/f
CL-V/f
OLV
Changed parameter setting values are stored as the user parameter default
settings used when the drive is initialized.
on the keypad stores the user parameter setting value. Once the setting value
on the keypad clears the user parameter setting value. Parameter o2-03 is
V/f
CL-V/f
OLV
Configures the Drive Model code for the corresponding Drive Model. This
parameter must be configured when control boards are replaced.
V/f
CL-V/f
OLV
Selects whether or not the
reference value with the keypad when in Drive Mode.
does not need to pressed. The drive stores the frequency reference 5 seconds after the
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
to stop operation, turn the external Run command off and then
Description
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
must be pressed to change the frequency
and
on the keypad.
Default Setting
(Setting Range)
0
(0 - 2)
Default Setting
(Setting Range)
Determined by the
drive
(-)
Default Setting
(Setting Range)
0
(0, 1)