11.8 H: Terminal Functions
4: Frequency Detection 1
Setting
Function
4
Frequency Detection
1
Note:
• The detection function operates regardless of the direction of motor rotation. The value of L4-01 is used as the forward/reverse
detection level.
• When using Closed Loop Vector Control, the motor speed is used as the reference.
ON : The output frequency is less than the value of L4-01 or does not exceed the value of L4-01 +
L4-02.
OFF : The output frequency exceeds the value of L4-01 + L4-02.
Note:
This time chart represents the result of the configuration when L4-07 = 1 [Speed Agree Detection Selection = Detection always
enabled]. The default setting of L4-07 is 0 [No detection during baseblock]. When the speed agreement detection selection is set to No
detection during baseblock, the terminal is off when the drive has cut output.
5: Frequency Detection 2
Setting
Function
5
Frequency Detection
2
Note:
• The detection function operates regardless of the direction of motor rotation. The value of L4-01 is used as the forward/reverse
detection level.
• When using Closed Loop Vector Control, the motor speed is used as the reference.
ON : The output frequency exceeds the value of L4-01.
OFF : The output frequency is less than the value of "L4-01 - L4-02," or it does not exceed the
value of L4-01.
6: Drive Ready
Setting
Function
6
Drive Ready
788
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is higher than the value of L4-01 [Speed Agree
Detection Level] + L4-02 [Speed Agree Detection Width]. After the terminal turns off, the terminal
continues to remain off until the output frequency reaches the level set with L4-01.
Figure 11.89 Frequency Detection 1 Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is higher than the setting value of L4-01 [Speed
Agree Detection Level]. After the terminal turns on, the terminal continues to stay on until the
output frequency reaches the value of L4-01 - L4-02.
Figure 11.90 Frequency Detection 2 Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the drive is in the ready state and the drive is running.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM