E: Motor Parameters; E1: V/F Pattern For Motor 1 - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.6

E: Motor Parameters

E parameters cover drive input voltage, V/f pattern, and motor parameters.

E1: V/f Pattern for Motor 1

E1 parameters are used to set the drive input voltage and motor V/f characteristics. To switch drive operation
from one motor to another motor, set the V/f characteristics for motor 1.
V/f Pattern Settings
The drive uses a V/f pattern to adjust the output voltage relative to the frequency reference.
This product has been preconfigured with 15 voltage/frequency (V/f) patterns. Use E1-03 [V/f Pattern Selection]
to select the V/f pattern that is appropriate for the application.
Additionally, one custom V/f pattern is available. Set E1-03 = F [Custom] and then manually set parameters E1-
04 through E1-10.
Set
Specification
ting
Constant Trq_50Hz base_50Hz
0
max
Constant Trq_60Hz base_60Hz
1
max
Constant Trq_50Hz base_60Hz
2
max
Constant Trq_60Hz base_72Hz
3
max
Variable Trq_50Hz base_35%
4
mid V
Variable Trq_50Hz base_50%
5
mid V
Variable Trq_60Hz base_35%
6
mid V
Variable Trq_60Hz base_50%
7
mid V
High Start Trq_50Hz base_
8
125% V
High Start Trq_50Hz base_
9
165% V
High Start Trq_60Hz base_
A
125% V
High Start Trq_60Hz base_
B
165% V
High Freq_60Hz base_90Hz
C
max
High Freq_60Hz base_120Hz
D
max
High Freq_60Hz base_180Hz
E
max
Custom
F
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Table 11.36 Predefined V/f Patterns
Characteristic
Constant torque
For general purpose applications. This pattern is used when the load
torque is constant without any rotation speed such as that used for linear
conveyor systems.
Variable torque
This pattern is used for torque loads proportional to 2 or 3 times the
rotation speed, such as is the case with fans and pumps.
High starting
This pattern is used when strong torque is required during startup.
torque
Constant output
This pattern is used to rotate motors at greater than 60 Hz. Output voltage
is constant when operating at greater than 60 Hz.
Constant torque
Enables a custom V/f pattern by changing E1-04 through E1-13 [V/f
Pattern for Motor 1]. The default settings for E1-04 through E1-13 are
equivalent to Setting Value 1 [Constant Trq_60Hz base_60Hz max].
11.6 E: Motor Parameters
Application
11
689